Parameters
Speed control under Real sensorless vector control, vector control, PM sensorless vector control
FR-A800
5 - 103
●
Adjust in the following procedure:
Change the Pr. 820 setting while checking the conditions.
If it cannot be adjusted well, change Pr. 821 setting, and perform
again.
No.
Movement / condition Adjustment method
1
Load inertia is high.
Set Pr. 820 and Pr. 821 higher.
Pr. 820
If acceleration is slow, raise the setting by 10%s and set a value that satisfies
the following condition:
The setting immediately before vibration/noise starts occurring × 0.8 to 0.9.
Pr. 821
If overshoots occur, raise the setting by double the setting and set a value that
satisfies the following condition:
The setting where overshoots stop occurring × 0.8 to 0.9.
2
Vibration or acoustic
noise are generated
from machines.
Set Pr. 820 lower and Pr. 821 higher.
Pr. 820
Lower the setting by 10%s and set a value that satisfies the following
condition:
The setting immediately before vibration/noise starts occurring × 0.8 to 0.9.
Pr. 821
If overshoots occur, raise the setting by double the setting and set a value that
satisfies the following condition:
The setting where overshoots stop occurring × 0.8 to 0.9.
3
Response is slow.
Set Pr. 820 higher.
Pr. 820
If acceleration is slow, raise the setting by 5%s and set a value that satisfies the
following condition:
The setting immediately before vibration/noise starts occurring × 0.8 to 0.9.
4
Return time (response
time) is long.
Set Pr. 821 lower.
Lower Pr. 821 by half the current setting and set a value that satisfies the following
condition:
The setting immediately before overshoots or unstable movements stop occurring × 0.8
to 0.9
5
Overshoots or unstable
movements occur.
Set Pr. 821 higher.
Raise Pr. 821 by double the current setting and set a value that satisfies the following
condition:
The setting immediately before overshoots or unstable movements stop occurring × 0.8
to 0.9
Tab. 5-36:
Adjustment procedures for parameter 820 and 821
NOTES
When adjusting the gain manually, set Pr. 819 "Easy gain tuning selection" to "0" (no easy gain tun-
ing) (initial value).
Pr. 830 "Speed control P gain 2" and Pr. 831 "Speed control integral time 2" are valid when terminal
RT is ON. In this case, replace them for Pr. 820 and Pr. 821 in the description above.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......