(N) Operation via communication and its settings
Parameters
5 - 624
Inverter status
monitor
(extended)
Read
H79
The states of the output signals such as forward rotation,
reverse rotation and inverter running (RUN) can be monitored.
(For the details, refer to page 5-628.)
4 digits
(B.E/D)
Inverter status
monitor
Read
H7A
2 digits
(B.E1/D)
Set frequency
(RAM)
Read
H6D
Read the set frequency/speed from the RAM or EEPROM.
H0000 to HFFFF: Set frequency in 0.01Hz increments
(The display can be changed to the rotations per minute using
Pr. 37, Pr. 144 and Pr. 811. (Refer to page 5-324))
4 digits
(B.E/D)
Set frequency
(EEPROM)
H6E
Set frequency
(RAM)
Write
HED
Write the set frequency/speed into the RAM or EEPROM.
H0000 to HE678 (0 to 590.00Hz): frequency in 0.01Hz
increments
(The display can be changed to the rotations per minute using
Pr. 37, Pr. 144 and Pr. 811. (Refer to page 5-324))
To change the set frequency consecutively, write data to the
inverter RAM. (Instruction code: HED)
4 digits
(A, C/D)
Set frequency
(RAM, EEPROM)
HEE
Inverter reset
Write
HFD
H9696: Inverter reset
As the inverter is reset at the start of communication by the
computer, the inverter cannot send reply data back to the
computer.
4 digits
(A, C/D)
H9966: Inverter reset
When data is sent normally, ACK is returned to the computer,
and then the inverter is reset.
4 digits
(A, D)
Faults history
batch clear
Write
HF4
H9696: Faults history batch clear
4 digits
(A, C/D)
Parameter clear
All clear
Write
HFC
All parameters return to initial values.
Whether to clear communication parameters or not can be
selected according to the data.
앫
Parameter clear
H9696: Communication parameters are cleared.
H5A5A: Communication parameters are not cleared.
앫
All parameter clear
H9966: Communication parameters are cleared.
H55AA: Communication parameters are not cleared.
For the details of whether or not to clear parameters, refer to
page A-5.
When a clear is performed with H9696 or H9966,
communication related parameter settings also return to the
initial values. When resuming the operation, set the
parameters again.
Performing a clear will clear the instruction code HEC, HF3, and
HFF settings.
Only H9966 and H55AA (all parameter clear) are valid during
the password lock (refer to page 5-207).
4 digits
(A, C/D)
Parameter
Read
H00 to H63 Refer to the instruction code (page A-5) and write and/or read
parameter values as required.
When setting Pr. 100 and later, the link parameter extended
setting must be set.
4 digits
(B.E/D)
Write
H80 to HE3
4 digits
(A, C/D)
Link parameter
Extended setting
Read
H7F
Parameter settings are switched according to the H00 to H0D
settings.
For details of the settings, refer to the instruction code
(page A-5).
2 digits
(B.E1/D)
Write
HFF
2 digits
(A1, C/D)
Second
parameter
changing
(instruction code
HFF = 1, 9)
Read
H6C
When setting the calibration parameters
H00: Frequency
#
H01: Parameter-set analog value
H02: Analog value input from terminal
2 digits
(B.E1/D)
Write
HEC
2 digits
(A1, C/D)
Multi command
Write/
Read
HF0
Available for writing 2 commands, and monitoring 2 items for
reading data (refer to page 5-629 for detail)
10 digits
(A2, C1/D)
Item
Read/
Write
Instruc-
tion
code
Data description
Number of
data digits
(Format)
Tab. 5-274:
Setting of the instruction codes and data (2)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......