Parameters
(A) Application parameters
FR-A800
5 - 535
PID output suspension function (SLEEP function) (SLEEP signal, Pr. 575 to Pr. 577)
●
When a status where the output frequency after PID calculation is less than Pr. 576 "Output
interruption detection level" has continued for the time set in Pr. 575 "Output interruption
detection time" or longer, inverter running is suspended. This allows the amount of energy
consumed in the inefficient low-speed range to be reduced.
●
When the deviation (for instance, the set point - measured value) reaches the PID output shutoff
release level (Pr. 577 setting value -1000%) while the PID output suspension function is activated,
the PID output suspension function is released, and PID control operation is automatically
restarted.
●
Whether to allow motor to coast to a stop or perform a deceleration stop when SLEEP operation
is started can be selected using Pr. 554.
●
While the PID output suspension function is activated, the PID output interruption signal (SLEEP)
is output. During this time, the inverter running signal (RUN) turns OFF and the During PID control
activated signal (PID) turns ON.
●
For the terminal used for the SLEEP signal, set "70 (positive logic)" or "170 (negative logic)" in any
of Pr. 190 to Pr. 196 (output terminal function selection).
I002693E
Fig. 5-264:
Output interruption (SLEEP function)
RUN
SLEEP
PID
1000%
When Pr. 554 = "0 to 3", reverse operation (Pr. 128 = "10")
Deviation
Pr. 577
Output frequency
Pr. 576
Less than Pr. 575
Pr. 575 or more
SLEEP period
OFF
ON
Time
Cancel
level
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......