(A) Application parameters
Parameters
5 - 488
Set multiple brake sequence functions (Pr. 641)
●
When the second brake sequence function is set, it is possible to switch between and use two
types of brake sequence functions. Turning ON the RT signal enables the second brake sequence
function.
●
Select the operation of the second brake sequence function with Pr. 641 "Second brake sequence
operation selection".
●
Set "45" in any of Pr. 178 to Pr. 189 (input terminal function selection) to assign the Second brake
sequence open completion signal (BRI2) to the input terminal.
●
To use the Second brake opening request signal (BOF2), set "22 (positive logic)" or "122 (negative
logic)" in any of Pr. 190 to Pr. 196 (output terminal function selection) to assign the function to the
output terminal.
●
The method of setting the second brake sequence parameters is the same as that for the
corresponding first brake sequence function parameters.
●
Switchover of the brake sequence function by RT signal is valid when the inverter is stopped.
Protective function
If one of the following faults occur while the brake sequence function is enabled, the inverter trips,
shuts off output, and turns OFF the brake opening request signal (BOF).
Pr. 641 setting
Brake sequence function when the RT signal is ON
0 (initial value)
Normal operation (The first and second brake sequence functions invalid)
7
Second brake sequence mode 1
8
Second brake sequence mode 2
9999
First brake sequence mode is valid
Tab. 5-205:
Multiple brake sequence functions
Fault
indication
Description
E.MB1
When (Detection frequency) – (output frequency)
≥
Pr. 285 during encoder feedback control.
When Pr. 285 (Overspeed detection function) = "9999", overspeed is not detected.
E.MB2
When deceleration is not normal during deceleration operation from the set frequency to the frequency
set in Pr. 282 (when Pr. 284 = "1") (except stall prevention operation)
E.MB3
When the BOF signal turned ON while the motor is at a stop. (load slippage prevention function)
E.MB4
When more than 2 s have elapsed after the start command (forward or reverse rotation) is input, but the
BOF signal does not turn ON.
E.MB5
When more than 2 s have elapsed after the BOF signal turned ON, but the BRI signal does not turn ON.
E.MB6
When the inverter had turned ON the brake opening request signal (BOF), but the BRI signal turned OFF.
E.MB7
When more than 2 s have elapsed after the BOF signal turned OFF at a stop, but the BRI signal does not
turn OFF.
Tab. 5-206:
Protective functions
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......