Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 361
5.11.6 Output
terminal
function selection
Use the following parameters to change the functions of the open collector output terminals and re-
lay output terminals.
The initial value is for standard models and IP55 compatible models.
The initial value is for separated converter types.
Parameters referred to
Pr. 3
Base frequency
=>
Pr. 52
Operation panel main monitor selection
=>
Pr. 54
FM/CA terminal function selection
=>
Pr. 158
AM terminal function selection
=>
Pr.
Name
Initial
value
Initial set signal
Setting range
190
M400
RUN terminal function
selection
Open
collec-
tor
output
terminal
0
RUN (Inverter running)
0 to 8, 10 to 20, 22, 25 to 28, 30 to
36, 38 to 57, 60, 61, 63, 64, 67, 68,
70, 79, 84, 85, 90 to 99, 100 to 108,
110 to 116, 120, 122, 125 to 128,
130 to 136, 138 to 157, 160, 161,
163, 164, 167, 168, 170, 179, 184,
185, 190 to 199, 200 to 208, 300 to
308, 9999
191
M401
SU terminal function
selection
1
SU (Up to frequency)
192
M402
IPF terminal function
selection
2
IPF (Instantaneous
power failure/
undervoltage)
9999
193
M403
OL terminal function
selection
3
OL (Overload warning)
194
M404
FU terminal function
selection
4
FU (Output frequency
detection)
195
M405
ABC1 terminal function
selection
Relay
output
terminal
99
ALM (Fault)
0 to 8, 10 to 20, 22, 25 to 28, 30 to
36, 38 to 57, 60, 61, 63, 64, 67, 68,
70, 79, 84, 85, 90, 91, 94 to 99, 100
to 108, 110 to 116, 120, 122, 125 to
128, 130 to 136, 138157, 160, 161,
163, 164, 167, 168, 170, 179, 184,
185, 190, 191, 194 to 199, 200 to
208, 300 to 308, 9999
196
M406
ABC2 terminal function
selection
9999
No function
Pr.
Name
Initial
value
Setting range
Description
289
M431
Inverter output terminal
filter
9999
5 to 50 ms
Set the time delay for the output terminal
response.
9999
No output terminal filter.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......