Parameters
(H) Protective function parameter
FR-A800
5 - 305
5.10.6
Initiating a protective function
A fault (protective function) is initiated by setting the parameter.
This function can be used to check how the system operates at activation of a protective function.
●
To initiate a fault (protective function), set the assigned number of the protective function you
want to initiate in Pr. 997.
●
The value set in Pr. 997 is not stored in EEPROM.
●
When a protective function activates, the inverter trips, a fault is displayed, and a fault signal (ALM,
ALM2) is output.
●
The latest fault in the faults history is displayed while the fault initiation function is in operation.
After a reset, the faults history goes back to the previous status. (The protective function gener-
ated by the fault is not saved in the faults history.)
●
Perform inverter reset to cancel the protective function.
●
For the selectable parameter by Pr. 997 and the corresponding protective functions, refer to page
6-9.
Pr.
Name
Initial
value
Setting
range
Description
997
H103
Fault initiation
9999
16 to 253
The setting range is same with the one for fault data
codes of the inverter (which can be read through
communication).
Written data is not stored in EEPROM.
9999
The read value is always "9999".
With this setting, the protective function does not
activate.
NOTES
If a protective function is already operating, no fault can be activated by Pr. 997.
The retry function is disabled when a protective function has been initiated by the fault initiation
function.
If a fault occurs after a protective function has been activated, the protective function indication
does not change. The fault is not saved in the faults history either.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......