Parameters
(A) Application parameters
FR-A800
5 - 513
Continuous multi-point orientation (V/F control, Advanced magnetic flux vector control)
●
Orientation command and orientation with STF/STR ON. (Orientation in servo-in status)
●
The position data is read at the rising edge of DY. (For the details, refer to the Instruction Manual
of FR-A8AX).
●
When the position signal is within the creep switchover position, the speed starts up to the creep
speed not to the orientation speed.
●
When the position signal is outside the creep switchover position, the speed starts up to the
orientation speed.
●
The DC injection brake operates if the position signal is within the DC injection brake start position.
●
16-bit data with the FR-A8AX is valid only when the DY signal is ON.
I001582E
Fig. 5-248:
Continuous multi-point orientation
NOTES
Couple the encoder with the motor shaft or with the shaft that stops the main shaft at the speci-
fied position. Couple it with the speed ratio of 1:1 and without any mechanical looseness.
The DC injection brake operates at orientation stop. Release the DC injection brake as soon as pos-
sible (within several seconds), as continuous operation of the DC injection brake will cause the
motor to overheat, leading to burnout.
Because the servo lock function is not available after orientation stop, provide a holding mecha-
nism, such as a mechanical brake or knock pin, when secure holding of the main shaft is required.
To ensure correct positioning, the encoder must be set in the proper rotation direction, and the A
and B phases must be connected correctly.
If the pulse signal from the encoder stops due to encoder signal loss, etc. during orientation, the
Orientation fault (ORM) signal may be output.
When performing orientation control, enable the DC injection brake. (Refer to page 5-663.) When
the DC injection brake is disabled, orientation operation cannot be completed.
When orientation control is performed, the DC injection brake operates regardless of the External
DC injection brake operation start (X13) signal even when Pr. 11 "DC injection brake operation
time" = "8888" (DC injection brake external selection).
Orientation speed (orientation switchover speed)
Creep speed (orientation deceleration ratio)
ON
ON
Main spindle speed (encoder)
Pr. 351
Pr. 352
Start signal
Orientation command
DY
Orientation complete signal
Position signal
ON
ON
Servo-in
Servo-in
50 ms or more is necessary
Position command latch
Position command latch
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......