Input terminal function assignment
●
Using Pr. 178 to Pr. 189, set the functions of the input terminals
●
Refer to the following table and set the parameters.
Setting
Signal
name
Function
Related parameter
Refer to
page
0
RL
Pr. 59 = 0 (initial
value)
Low-speed operation
command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
≠
Remote setting (setting clear)
Pr. 59
Stop-on-contact selection 0
Pr. 270, Pr. 275, Pr. 276
1
RM
Pr. 59 = 0 (initial
value)
Middle-speed operation
command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
≠
Remote setting (deceleration)
Pr. 59
2
RH
Pr. 59 = 0 (initial
value)
High-speed operation
command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
≠
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44 to Pr. 51, Pr. 450 to Pr. 463,
Pr. 569, Pr. 832, Pr. 836, etc.
Stop-on-contact selection 1
Pr. 270, Pr. 275, Pr. 276
4
AU
Terminal 4 input selection
Pr. 267
5
JOG
Jog operation selection
Pr. 15, Pr. 16
6
CS
Selection of automatic restart after instantaneous
power failure, flying start
Pr. 57, Pr. 58, Pr. 162 to Pr. 165,
Pr. 299, Pr. 611
Electronic bypass function
Pr. 57, Pr. 58, Pr. 135 to Pr. 139,
Pr. 159
7
OH
External thermal relay input
Pr. 9
8
REX
15-speed selection
(Combination with multi-speeds of RL, RM, and RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
9
X9
Third function selection
Pr. 110 to Pr. 116
10
X10
Inverter run enable signal (FR-HC2/FR-CV/FR-CC2
connection)
Pr. 30, Pr. 70, Pr. 599
11
X11
FR-HC2/FR-CC2 connection, instantaneous power
failure detection
Pr. 30, Pr. 70
12
X12
PU operation external interlock
Pr. 79
13
X13
External DC injection brake operation start
Pr. 10 to Pr. 12
14
X14
PID control valid terminal
Pr. 127 to Pr. 134, Pr. 575 to
Pr. 577
15
BRI
Brake opening completion signal
Pr. 278 to Pr. 285
16
X16
PU/External operation switchover
(External operation with X16-ON)
Pr. 79, Pr. 340
17
X17
Load pattern selection forward/reverse rotation
boost (For constant-torque with X17-ON)
Pr. 14
18
X18
V/F switchover (V/F control with X18-ON)
Pr. 80, Pr. 81, Pr. 800
19
X19
Load torque high-speed frequency
Pr. 270 to Pr. 274
20
X20
S-pattern acceleration/deceleration C switchover
Pr. 380 to Pr. 383
22
X22
Orientation command
(for FR-A8AP/FR-A8TP/FR-A8APR)
Pr. 350 to Pr. 369
23
LX
Pre-excitation/servo ON
Pr. 850
24
MRS
Output stop
Pr. 17
Electronic bypass function
Pr. 57, Pr. 58, Pr. 135 to Pr. 139,
Pr. 159
25
STP
(STOP)
Start self-holding selection
Pr. 250
26
MC
Control mode switchover
Pr. 800
27
TL
Torque limit selection
Pr. 815
28
X28
Start-time tuning start external input
Pr. 95
Tab. 5-167:
Input terminal function assignment (1)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......