Control method
Parameters
5 - 56
5.2.2
Changing the control method
Set the control method and control mode.
V/F control, Advanced magnetic flux vector control, Real sensorless vector control, Vector control,
and PM sensorless vector control are the control methods available for selection.
The control modes are speed control, torque control, and position control. These are set when se-
lecting Advanced magnetic flux vector control, Real sensorless vector control, Vector control, and PM
sensorless vector control. Select a control mode from speed control mode, torque control mode and
position control mode under Real sensorless vector control or vector control. The initial setting is V/
F control.
When using an IPM motor MM-CF, simply performing the IPM parameter initialization enables the PM
sensorless vector control and selects the speed control and position control.
●
Select a control method and control mode by using Pr. 800 (Pr. 451) "Control method selection".
●
The control mode can be switched using the mode switching signal (MC).
Pr.
Name
Initial
value
Setting range
Description
71
C100
Applied motor
0 to 6, 13 to 16, 20, 23,
24, 30, 33, 34, 40, 43, 44,
50, 53, 54, 70, 73, 74,
330, 333, 334, 8090,
8093, 8094, 9090, 9093,
9094
By selecting a standard motor or constant-
torque motor, the thermal characteristic and
motor constant of each motor are set.
80
C101
Motor capacity
9999
0.4 to 55 kW
Set the applied motor capacity.
0 to 3600 kW
9999
V/F control
81
C102
Number of motor poles
9999
2, 4, 6, 8, 10, 12
Set the number of motor poles.
9999
V/F control
83
C104
Rated motor voltage
200/400 V
0 to 1000 V
Set the rated motor voltage (V).
84
C105
Rated motor frequency
9999
10 to 400 Hz
Set the rated motor frequency (Hz).
9999
The setting value of Pr. 3 "Base frequency" is
used.
800
G200
Control method selection
20
0 to 6
Vector control
9
Vector control test operation
10 to 12
Real sensorless vector control
13, 14
PM sensorless vector control
20
V/F control
(Advanced magnetic flux vector control)
100 to 106
Vector control
Fast-response
operation
109
Vector control, PM
sensorless vector
control test operation
110 to 112
Real sensorless vector
control
110, 113, 114
PM sensorless vector
control
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......