The following shows the relationship between the input values of the analog input terminals, and
the set point and measured value.
Can be changed by Pr. 73 and Pr. 267 and the voltage/current input switch. (Refer to page 5-389.)
Selection of additive method for PID calculation result
When ratio is selected as the additive method (Pr. 128 = "42, 43"), PID calculation result × (ratio of main
speed) is added to the main speed.
The ratio is determined by the Pr. 125 "Terminal 2 frequency setting gain frequency" and C2 (Pr. 902)
"Terminal 2 frequency setting bias frequency" settings. In the initial status, 0 to 60 Hz is set for 0 to
100%. Thus, 60 Hz main speed is regarded as 100%, and the 30 Hz main speed is regarded as 50%.
Input
terminal
Inspect
specification
Relationship with analog input
Calibration parameter
Set point
Result
Terminal 2
0 to 5 V
0 V = 0%
5 V = 100%
0 V = 0%
5 V = 100%
Pr. 125, C2 to C4
0 to 10 V
0 V = 0%
10 V = 100%
0 V = 0%
10 V = 100%
0 to 20 mA
0 mA = 0%
20 mA = 100%
0 mA = 0%
20 mA = 100%
Terminal 1
0 to ±5 V
–5 V to 0 V = 0%
5 V = +100%
–5 V to 0 V = 0%
5 V = +100%
When Pr. 128 = "10"
Pr. 125, C2 to C4
When Pr. 128
≥
"1000"
C12 to C15
0 to ±10V
–10 V to 0 V = 0%
10 V = +100%
–10 V to 0 V = 0%
10 V = +100%
Terminal 4
0 to 5 V
0 V to 1 V = 0%
5 V = 100%
0 V to 1 V = 0%
5 V = 100%
Pr. 126, C5 to C7
0 to 10 V
0 V to 2 V = 0%
10 V = 100%
0 V to 2 V = 0%
10 V = 100%
0 to 20 mA
0 to 4 mA = 0%
20 mA = 100%
0 to 4 mA = 0%
20 mA = 100%
Tab. 5-238:
Relationship between the analog input and the set point and measured value
I002709E
Fig. 5-277:
Signal calibration at terminal 2
NOTES
Even if C4 (Pr. 903) is set to other than 100%, the frequency setting signal is treated as 100%.
Even if C3 (Pr. 902) is set to other than 0%, the frequency setting signal is treated as 0%.
If C2 (Pr. 902) is set to other than 0 Hz, the frequency setting signal is 0% at the C2 (Pr. 902) fre-
quency setting or below.
0
100%
Initial value
Frequency setting signal
Bias
C2 (Pr. 902)
60 Hz
Output fr
eque
nc
y
Gain
Pr. 125
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......