(D) Operation command and frequency command
Parameters
5 - 288
5.9.7
Operation by multi-speed setting
Use these parameters to change among pre-set operation speeds with the terminals. The speeds are
pre-set with parameters.
Any speed can be selected by simply turning ON/OFF the contact signals (RH, RM, RL, and REX signals).
Multi-speed setting (Pr. 4 to Pr. 6)
The inverter operates at frequencies set in Pr. 4 when RH signal is ON, Pr. 5 when RM signal is ON and
Pr. 6 when RL signal is ON.
Pr.
Name
Initial value
Setting
range
Description
FM
CA
28
D300
Multi-speed input compensation
selection
0
0
Without compensation
1
With compensation
4
D301
Multi-speed setting (high speed)
60 Hz
50 Hz
0 to 590 Hz
Sets the frequency when RH is ON.
5
D302
Multi-speed setting (middle speed)
30 Hz
0 to 590 Hz
Sets the frequency when RM is ON.
6
D303
Multi-speed setting (low speed)
10 Hz
0 to 590 Hz
Sets the frequency when RL is ON.
24
D304
Multi-speed setting (speed 4)
9999
0 to 590 Hz,
9999
Frequency from 4th speed to 15th
speed can be set according to the
combination of the RH, RM, RL and
REX signals.
9999: Not selected
25
D305
Multi-speed setting (speed 5)
26
D306
Multi-speed setting (speed 6)
27
D307
Multi-speed setting (speed 7)
232
D308
Multi-speed setting (speed 8)
233
D309
Multi-speed setting (speed 9)
234
D310
Multi-speed setting (speed 10)
235
D311
Multi-speed setting (speed 11)
236
D312
Multi-speed setting (speed 12)
237
D313
Multi-speed setting (speed 13)
238
D314
Multi-speed setting (speed 14)
239
D315
Multi-speed setting (speed 15)
I002436E, I002444E
Fig. 5-118:
Multi-speed selection by external terminals
RM
STF
STR
RH
SD
RL
RH
RM
RL
Inverter
Forward rotation start
Reverse rotation start
High speed
Middle speed
Low speed
Switch
Ou
tput fr
equen
cy
[H
z]
ON
ON
ON
Time
Speed 3 (Low speed)
Speed 2 (Middle speed)
Speed 1 (High speed)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...