Parameters
(A) Application parameters
FR-A800
5 - 475
,
The RES signal can be used for reset input acceptance with Pr. 75 "Reset selection/disconnected
PU detection/PU stop selection". When RES signal and another input signal are simultaneously
input, the MC operation by the RES signal has a higher priority.
$
MC1 turns OFF at an inverter fault.
%
When Pr. 138 ="0 (electronic bypass invalid at a fault)", MC2 is OFF. When Pr. 138 ="1 (electronic
bypass valid at a fault)", MC2 is ON.
&
MC operation
: MC-ON
×: MC-OFF
⎯
:
During inverter operation, MC2-OFF, MC3-ON
During commercial power supply operation, MC2-ON, MC3-OFF
Invariance:
The status before changing the signal ON or OFF is held.
●
The output signals are as shown below.
Electronic bypass operation sequence
●
Example of operation sequence without automatic bypass sequence (Pr. 139 = "9999")
Signal
Applied terminal
(Pr. 190 to Pr. 196 setting)
Description
MC1
17
Operation output signal of the magnetic contactor MC1 on the
inverter's input side.
MC2
18
Operation output signal of the magnetic contactor MC2 for the
commercial power supply operation.
MC3
19
Operation output signal of the magnetic contactor MC3 on the
inverter's output side.
Tab. 5-200:
Output signals
I002669E
Fig. 5-222:
Signal timing when there is no automatic switchover sequence
Inverter run command
(STF)
Power supply
Operation interlock
(MRS)
Inverter/commercial
power supply (CS)
Inverter input side MC
(MC1)
Inverter output side MC
(MC3)
MC for commercial
power supply operation
(MC2)
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Each timer
Operating status
(motor speed)
INV
operation
Coasting Bypass
operation
Coasting
INV
operation
Stop
Pr. 57
Pr. 137
Pr. 58
Pr. 136
Pr. 136
Pr. 57
Off only at inverter alarm
ON : Operation enabled
OFF: Operation disabled
ON : Forward rotation
OFF: Stop
ON : Inverter operation
OFF: Commercial power supply operation
Indicates the delay time until
the MC turns on (off ).
Pr. 136 MC switchover interlock time
Pr. 137 MC3 start (waiting time)
Pr. 57 Reset time
Pr. 58 Switchover cushion time
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......