(A) Application parameters
Parameters
5 - 572
Selection of restart operation (Pr. 162)
●
At a power restoration, the encoder detects the motor speed by a frequency search so that the
inverter can re-start smoothly.
●
The encoder also detects the rotation direction so that the inverter can re-start smoothly even
during the reverse rotation.
●
When "10 (11, 12, 13)" is set in Pr. 162, a restart operation is performed at each start and automatic
restart after instantaneous power failure. When "0 (1, 2)" is set to Pr. 162, a restart operation is
performed at the first start after a power-ON, and from the second power-ON onwards, a start
from the starting frequency is performed.
NOTES
The CS signal is assigned to the CS terminal in the initial status.By setting "6" in any of Pr. 178 to
Pr. 189 (input terminal function selection), the signal can be assigned to another terminal. Chang-
ing the terminal assignment may affect other functions. Set parameters after confirming the func-
tion of each terminal.
If the CS signal is not assigned to any input terminal, solely setting Pr. 57 will enable the restart
operation at all times.
If the restart operation is selected, instantaneous power failure protection (E.IPF) is disabled while
the fault output signal is output at an instantaneous power failure.
The SU and FU signals are not output during the restart. These signals are output after the restart
cushion time passes.
Restart operation is also performed after the inverter reset is released or after the retry by the retry
function occurs.
The automatic restart after instantaneous power failure function is invalid when the load torque
high-speed frequency control (Pr. 270 = "2, 3, 13") is set.
I002716E
Fig. 5-288:
Restart operation
NOTES
Because a DC injection brake is applied instantaneously at speed detection during a restart, the
speed might drop if the moment of inertia (J) of the load is small.
Restart operation with reduced voltage is not available for PM sensorless vector control.
+
∗
Instantaneous (power failure) time
Power supply
(R/L1,S/L2,T/L3)
Motor
speed N (r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E (V)
Coasting
time (Pr. 57)
Speed
detection
time
Acceleration time
at a restart
(Pr. 611 setting)
* The output shut off timing differs
according to the load condition
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......