Parameters
(H) Protective function parameter
FR-A800
5 - 307
5.10.8 Retry
function
This function allows the inverter to reset itself and restart at activation of the protective function (fault
indication). The retry generating protective functions can be also selected.
When the automatic restart after instantaneous power failure function is selected (Pr. 57 "Restart
coasting time" ≠ 9999), the restart operation is also performed after a retry operation as well as after
an instantaneous power failure. (Refer to page page 5-562 and page 5-571 for the restart operation.)
Setting the retry function (Pr. 67, Pr. 68)
●
When the inverter protective function is operating (fault indication), the retry function automat-
ically cancels (resets) the protective function after the time set in Pr. 68. The retry function then
restarts the operation from the starting frequency.
●
Retry operation is enabled when Pr. 67 ≠ "0". For Pr. 67, set the number of retries at activation of
the protective function.
●
When retries fail consecutively more than the number of times set in Pr. 67, a retry count excess
(E.RET) occurs, resulting in an inverter retries. (Refer to the retry failure example.)
●
Use Pr. 68 to set the waiting time from a protective function activation to a retry in the range of
0.1 to 600 s.
●
During retry operation, the during retry (Y64) signal is ON. For the Y64 signal, set "64 (positive
operation)" or "164 (negative operation)" in any of Pr. 190 to Pr. 196 (output terminal function
selection) to assign the function.
Pr.
Name
Initial
value
Setting
range
Description
65
H300
Retry selection
0
0 to 5
A retry-making fault can be selected.
(Refer to tab. 5-119 on page 5-308.)
67
H301
Number of retries at fault
occurrence
0
0
No retry function
1 to 10
Set the number of retries at a fault occurrence.
A fault output is not provided during the retry
operation.
101 to 110
Set the number of retries at a fault occurrence.
(The setting value minus 100 is the number of retries.)
A fault output is provided during the retry operation.
68
H302
Retry waiting time
1 s
0.1 to 600 s Set the waiting time from a fault occurrence to a retry.
69
H303
Retry count display erase
0
0
Clears the number of successful restarts made by
retries.
Pr. 67 setting
Fault output during retry operation
Retry count
0
⎯
No retry function
1 to 10
Not provided
1 to 10 times
101 to 110
Provided
1 to 10 times
Tab. 5-118:
Setting the retry function parameters
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......