The maintenance-free microprocessor-controlled room sensor 

AERASGARD

® 

RTM - CO

2

 - SD 

 

with automatic  calibration  (fixed) is used for detecting the 

CO

2

 content of the air within a range of 0...2000 ppm and the temperature within a range of 0...+50°C. The measured values are converted into 

standard signals of 0 -10 V.
The maintenance-free microprocessor-controlled room sensor 

AERASGARD

®

  RFTM - LQ

 

- CO

2

 - W

 

and 

RCO

2

 - W 

RLQ - CO

2

 - W 

with automatic calibration 

(can be deactivated via DIP switches) is used for detecting the overall room climate. It measures CO

2

 within a range of 0...2000 ppm or 0...5000 ppm, air 

quality (VOC) in one of three sensitivity levels that can be selected LOW  /  MEDIUM (default)  /  HIGH, temperature within a range of 0...+50°C as well as 
relative humidity of 0...100 %  r.H. The measured values are converted into standard signals of 0 -10 V oder 4...20 mA  (selectable via DIP switches). As an 
option, the measured values can be shown continuously in the illuminated display.
Elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment, for installation on vertically or horizontally installed in-wall flush boxes, 
with predetermined breaking point for on-wall cable entry. 
The relative humidity (% r.H.) quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature.  
A digital, long-term stable sensor used as measuring element for relative air humidity and temperature guarantees exact measurement results. The air 
quality is determined based on a (VOC) gas mixture sensor. The CO

2

 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red 

technology). 

TECHNICAL DATA

Voltage supply:  

24 V AC ⁄ DC (± 10 %)

Power  consumption:  

RCO

2

 - W  ⁄  RTM - CO

2

 - SD

 

  

< 1.5 W ⁄ 24 V DC  typical;  < 2.9 VA ⁄ 24 V AC typical;  peak current 200  mA 

 RLQ - CO

2

 - W   ⁄   RFTM - LQ - CO

2

 - W

 

:

    

< 4.4 W ⁄ 24 V DC  typical;  < 6.4 VA ⁄ 24 V AC typical;  peak current 200  mA 

Outputs: 

RTM - CO

2

 - SD 

0 -10 V  (fixed)   

Rxx - CO

2

 - W 

 

  0 -10 V   

or

   4...20 mA,  working  resistance  < 800  Ω     

 

(selectable via DIP switches, selected variant applies for all outputs), 

 

with offset potentiometer (± 10 % of the measuring range) 

Relay  output:  

RTM - CO

2

 - SD 

without changeover contact 

Rxx - CO

2

 - W  

with potential-free

 changeover contact

  (24 V / 1 A)     

 

(assignment selectable via DIP switches, switchpoint adjustable)

HUMIDITY

Sensors:  

digital humidity sensor with integrated temperature sensor,  

low hysteresis, high long-term stability

Measuring  range,  humidity:  

0...100 %  r. H.   

Operating range, humidity:  

0...95 % r. H.  (without dew formation)

Deviation, humidity: 

typically 

± 2.0 % 

(20...80 %  r. H.)  at  +25 °C,  otherwise  ± 3.0 %

Output,  humidity:  

0 -10 V 

or

 4...20 mA  (selectable via DIP switches)

TEMPERATURE 

Measuring  range,  temperature:  

0...+ 50 °C

Operating  range,  temperature:  

0...+ 50 °C

Temperature  deviation:  

± 0.2 K  at  +25 °C

Output,  temperature:  

RTM - CO

2

 - SD 

0 -10 V   (fixed) 

Rxx - CO

2

 - W 

  

  0 -10 V   

or

  4...20 mA  (selectable via DIP switches)

AIR QUALITY  (VOC)

Sensor, VOC : 

VOC sensor (metal oxide) (VOC = volatile organic compounds), 
with manual calibration (via zero button) and 
with automatic calibration (can be deactivated via DIP switches)

Measuring range, VOC : 

0...100 % air quality; referred to calibrating gas; 

multi-range switching

 (selectable via DIP switches) 

VOC sensitivity low, medium, high

Output,  VOC : 

0 -10 V    (0 V  =  clean  air,  10 V  =  polluted  air) 

or

  4...20 mA   

(selectable via DIP switches, switchpoint can be adjusted from 0...100 % of the output signal)

Measuring accuracy, VOC : 

± 20 % of final value  (referred to calibrating gas) 

Service life: 

> 60 months  (under normal load conditions)

CARBON DIOXIDE (CO

2

)

Sensor, CO

2

:   

optical NDIR sensor (non-dispersive infra-red technology), 
with manual calibration (via zero button),

 

RTM - CO

2

 - SD 

with automatic calibration (fixed)

 

Rxx - CO

2

 - W 

 

  

with automatic calibration (can be deactivated via DIP switches)

Measuring range, CO

2

:   

RTM - CO

2

 - SD 

0...2000  ppm   (fixed)

 

Rxx - CO

2

 - W 

 

 

0...2000  ppm   

or

  0...5000  ppm  (selectable via DIP switches)

Output, CO

2

:  

RTM - CO

2

 - SD 

0 -10 V   (fixed) 

Rxx - CO

2

 - W 

 

  0 -10 V   

or

  4...20 mA  (selectable via DIP switches)

Measuring accuracy, CO

2

:  

± 30 ppm  ± 3 %  of  measured  value

Temperature dependence, CO

2

:  

± 5 ppm   ⁄  °C  or  ± 0.5 %  of  measured  value   ⁄  °C     
(whichever is higher)  

(continued on next page!)

Summary of Contents for AERASGARD RCO2-W

Page 1: ...RTM CO2 SD 0 10 V fixed Rxx CO2 W 0 10 V or 4 20 mA working resistance 800 selectable via DIP switches selected variant applies for all outputs with offset potentiometer 10 of the measuring range Rela...

Page 2: ...50 C 0 2000 5000 ppm 0 100 W 1501 61B8 7321 200 Outputs 0 10V or 4 20mA selectable via DIP switches selected variant applies for all outputs Standard room sensor RTM CO2 SD with fixed output 0 10 V E...

Page 3: ...FF OFF VOC 10 95 ON OFF Temperature 5 48 C OFF ON Humidity 10 95 r H ON ON Output DIP 9 Voltage 0 10 V default OFF Current 4 20 mA ON Note DIP 5 is not assigned 4 5 6 1 2 3 SET REL OFFSET ZERO CO CO V...

Page 4: ...ly of the DIP switch position Sufficient fresh air must be provided before and after the calibration procedure We recommend a fresh air supply of at least two hours before the calibration process The...

Page 5: ...surands the corresponding lower limit is used directly as a basis VOC 10 95 Temperature 5 48 C Humidity 10 95 r H The assignment of the switch output to measurand is done via DIP switch DIP 7 and DIP...

Page 6: ...everse polarity protection diode is integrated in this device variant This internal one way rectifier on AC supply voltage The output signal is to be tapped by a measuring instrument The output signal...

Page 7: ...es must only be connected to safety extra low voltage and under dead voltage condition To avoid damages and errors the device e g by voltage induction shielded cables are to be used laying parallel wi...

Reviews: