background image

15

G  

Mounting and Installation

Humidity table  

MR:   0...100 %  r. H.

%  

r.H.

U

A   

in V

I

A   

in mA

%  

r.H.

U

A   

in V

I

A   

in mA

 0

0

4.0

50

5.0

12.0

 5

0.5

4.8

55

5.5

12.8

10

1.0

5.6

60

6.0

13.6

15

1.5

6.4

65

6.5

14.4

20

2.0

7.2

70

7.0

15.2

25

2.5

8.0

75

7.5

16.0

30

3.0

8.8

80

8.0

16.8

35

3.5

9.6

85

8.5

17.6

40

4.0

10.4

90

9.0

18.4

45

4.5

11.2

95

9.5

19.2

Continued at the right ...

100

10.0

20.0

Temperature table  

MR:   0...+50 °C

°C

U

A   

in V

I

A   

in mA

 0

0

4.0

 5

1.0

5.6

10

2.0

7.2

15

3.0

8.8

20

4.0

10.4

25

5.0

12.0

30

6.0

13.6

35

7.0

15.2

40

8.0

16.8

45

9.0

18.4

50

10.0

20.0

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

Circuitry

Circuitry

Output

0V/GND

Output

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

Output

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier on AC  supply voltage. 

The output signal is to be tapped by a measuring instrument. The output 
signal is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Summary of Contents for AERASGARD RCO2-W

Page 1: ...RTM CO2 SD 0 10 V fixed Rxx CO2 W 0 10 V or 4 20 mA working resistance 800 selectable via DIP switches selected variant applies for all outputs with offset potentiometer 10 of the measuring range Rela...

Page 2: ...50 C 0 2000 5000 ppm 0 100 W 1501 61B8 7321 200 Outputs 0 10V or 4 20mA selectable via DIP switches selected variant applies for all outputs Standard room sensor RTM CO2 SD with fixed output 0 10 V E...

Page 3: ...FF OFF VOC 10 95 ON OFF Temperature 5 48 C OFF ON Humidity 10 95 r H ON ON Output DIP 9 Voltage 0 10 V default OFF Current 4 20 mA ON Note DIP 5 is not assigned 4 5 6 1 2 3 SET REL OFFSET ZERO CO CO V...

Page 4: ...ly of the DIP switch position Sufficient fresh air must be provided before and after the calibration procedure We recommend a fresh air supply of at least two hours before the calibration process The...

Page 5: ...surands the corresponding lower limit is used directly as a basis VOC 10 95 Temperature 5 48 C Humidity 10 95 r H The assignment of the switch output to measurand is done via DIP switch DIP 7 and DIP...

Page 6: ...everse polarity protection diode is integrated in this device variant This internal one way rectifier on AC supply voltage The output signal is to be tapped by a measuring instrument The output signal...

Page 7: ...es must only be connected to safety extra low voltage and under dead voltage condition To avoid damages and errors the device e g by voltage induction shielded cables are to be used laying parallel wi...

Reviews: