Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 343
Differs according to capacities. (FR-A820-03160(55K) or lower, FR-A840-01800(55K) or lower/
FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher)
When the output current is less than the specified current level (5% of the rated inverter current),
the output current is monitored as 0 A. Therefore, the monitored value of an output current and
output power may be displayed as "0" when using a much smaller-capacity motor compared to
the inverter or in other instances that cause the output current to fall below the specified value.
Setting of Pr. 1018 "Monitor with sign selection" is required.
#
The setting is available only for standard models.
,
The setting is available only with terminal AM (Pr. 158).
Torque monitor (power
driving/regenerative
driving polarity
switching)
0.1 %
36
Pr. 866
Motor temperature
1 °C
46
Pr. 751
Enabled when the FR-A8AZ
is used.
Energy saving effect
Changeable
by parameter
setting
50
Inverter capacity
Regarding the energy
saving monitor, refer to
page 5-189
PID set point
0.1%
52
100%
Refer to page 5-537 for the
PID control.
PID measured value
0.1%
53
100%
PID deviation
0.1%
100%
Output with a negative sign
(terminal AM)
Motor thermal load
factor
0.1%
61
Motor thermal
operation level
(100%)
Inverter thermal load
factor
0.1%
62
Inverter thermal
operation level
(100%)
PID measured value 2
0.1%
67
100%
PLC function analog
output
0.1%
70
100%
Refer to page 5-587 for the
PLC function.
Remote output value 1
0.1%
87
100%
Refer to page 5-382 for the
analog remote output.
Remote output value 2
0.1%
88
100%
Remote output value 3
0.1%
89
100%
Remote output value 4
0.1%
90
100%
PID manipulated
variable
0.1%
100%
Output with a minus sign
(terminal AM)
Second PID set point
0.1%
92
100%
Refer to page 5-537 for the
PID control.
Second PID measured
value
0.1%
93
100%
Second PID deviation
0.1%
200%
Second PID measured
value 2
0.1%
95
100%
Second PID manipulated
variable
0.1%
100%
Dancer main speed
setting
0.01 Hz
97
Pr. 55
Refer to page 5-552 for the
dancer control.
Control circuit
temperature
1 °C
98
100 °C
Terminal FM/CA: 0 to 100°C
Terminal AM: -20 to 100°C
Types of monitor
Unit
Pr. 54
(FM/CA)
Pr. 158 (AM)
setting
Terminal
FM, CA, AM
Full-scale value
Negative
(-) output
Remarks
Tab. 5-135:
Monitor description list (2)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......