Protective functions
Causes and corrective actions
FR-A800
6 - 27
Operation panel
indication
E.OP1 to E.OP3
to
FR-LU-08
Option1 Fault to
Option3 Fault
Name
Communication option fault
Description
앫
The inverter trips if a communication line error occurs in the communication option.
앫
When the FR-A8APR is installed to the inverter and a motor with a resolver is used, the
inverter trips if the FR-A8APR fails or the wiring of the resolver is not properly connected.
Check point
앫
Check for an incorrect option function setting and operation.
앫
Check that the plug-in option is plugged into the connector properly.
앫
Check for a break in the communication cable.
앫
Check that the terminating resistor is fitted properly.
앫
Check that the wiring of the resolver is correct. (When the FR-A8APR is used)
Corrective action
앫
Check the option function setting, etc.
앫
Connect the plug-in option securely.
앫
Check the connection of communication cable.
앫
Check the wiring of the resolver. (When the FR-A8APR is used)
앫
If the fault occurs again when the inverter is reset, contact your sales representative.
Operation panel
indication
E.16 to E.20
to
FR-LU-08
Fault 16 to Fault 20
Name
User definition error by the PLC function
Description
The protective function is activated by setting "16 to 20" in the special register SD1214 for the
PLC function. The inverter trips when the protective function is activated.
The protective function is activated when the PLC function is enabled. This protective function is
not available in the initial setting (Pr. 414 = "0").
Any character string can be displayed on FR-LU08 or FR-PU07 by sequence programs.
Check point
앫
Check if "16 to 20" is set in the special register SD1214.
Corrective action
앫
Set a value other than "16 to 20" in the special register SD1214.
Operation panel
indication
E.PE
FR-LU-08
Corrupt Memory
Name
Parameter storage device fault (control circuit board)
Description
The inverter trips if a fault occurs in the parameter stored. (EEPROM failure)
Check point
Check for too many numbers of parameter write times.
Corrective action
Please contact your sales representative.
Set "1" in Pr. 342 "Communication EEPROM write selection" (write to RAM) for the operation
which requires frequent parameter writing via communication, etc. Note that writing to RAM
goes back to the initial status at power OFF.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......