User & Technical Manual 

NE010 & NE015 50 Hz Series 

Rev 1.9 

 
 

 

 

 

Summary of Contents for NE010 Series

Page 1: ...User Technical Manual NE010 NE015 50 Hz Series Rev 1 9...

Page 2: ...y unit specifications 1 7 02 19 19 B Slotnick Updated mounting instructions alarm settings RMA procedure 1 8 04 04 19 B Slotnick Added neutral power designation to schematic 1 9 06 19 19 B Slotnick Up...

Page 3: ...4 Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller Programmi...

Page 4: ...pment Thermal Edge air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment u...

Page 5: ...l panel and wiring and to prevent personal injury assure that the power source is compatible with the equipment before operating When recharging refrigeration type and amount must be the same as shown...

Page 6: ...proper circuit protection sizing Connect a power source to the air conditioner and turn on the power switch The evaporator fan will start and the digital controller will power up If cooling is called...

Page 7: ...from inside the enclosure use the fasteners supplied to attach the air conditioner to the enclosure Screw all fasteners hand tight Then torque to 96 in lbs These fasteners should be checked periodical...

Page 8: ...s SCCR Short Circuit Current Rating Amps Recommended Fuse Selection Amps KVA Rating Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi NE010105 90 110 12 1 2 3 2 4 Amp Class CC CCM...

Page 9: ...VA Rating Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi NE015105 90 110 12 2 2 4 2 4 Amp Class CC CCMR Time Delay 0 3 R134a 7 75 76 178 NE015205 180 220 11 6 1 9 2 7 Amp Class...

Page 10: ...Contact is programmed with an individual dry contact set point to monitor the enclosure temperature limit that you require When the enclosure temperature has exceeded the maximum limit the Form C gol...

Page 11: ...onditioners have a Special Programming option for selecting unique pre in programmed settings for special requirements Although most parameters are accessible in our digital controller this option all...

Page 12: ...refer to the Ethernet IP Option Specifications included with the Air Conditioner Remote Controller When having our Programmable Digital Controller mounted on the face of our Air Conditioner does not...

Page 13: ...thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may have occurred...

Page 14: ...lue 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a key Note The set value is stored even when the procedur...

Page 15: ...mperature Alarm P2 171 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Output 2 CA Evaporator Coil Alarm Low Pressure for 2 minutes Compressor Off 2 noP I...

Page 16: ...to enhance air filter efficiency Replacement filters are readily available from THERMAL EDGE Customer Service DO NOT operate the air conditioner without the air filter Such operation will allow the co...

Page 17: ...ture Probe Mounting Clip 52126 250C Thermal Expansion Value TXV 32023 1 Compressor 31511 1 for 100VAC 31512 1 for 200VAC Gasket Installation Kit 71300 N115 Evaporator Fan NE010 41003 1 1 for 100VAC 41...

Page 18: ...the UL label YES If problem is still present contact technical support Unit Not Cooling Is Compressor On YES NO Is evaporator Fan on YES NO Measure Temperature at Evaporator Verify Heat Load Requireme...

Page 19: ...1 or P2 YES NO Check contactor circuit Does it have power 3 NO YES Refer to Alarm Signals in Digital Temperature Controller Programming Section Contact Customer Support NO YES Verify contact coil is b...

Page 20: ...ical specification Verify proper recommended fuse has been selected Check compressor if excess heat present compressor may be faulty Contact Technical Support Water overflow excessive Check drain is i...

Page 21: ...1800 Hurd Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email support thermal edge com SP ENG 210 001 09 Rev 1 9 21 P a g e Physical Dimensions...

Page 22: ...1800 Hurd Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email support thermal edge com SP ENG 210 001 09 Rev 1 9 22 P a g e...

Page 23: ...G 210 001 09 Rev 1 9 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in this document If y...

Page 24: ...y in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental conditions without the proper filtratio...

Page 25: ...Number Serial Number Customer name and contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available Air Cond...

Page 26: ...connect the wires by inserting them into the lower receptacles located on the front of connector in the following order NOTE If using stranded wires it may be difficult to insert into the receptacles...