Installation and wiring
Control circuit
FR-A800
2 - 47
2.6.4 Wiring
precautions
●
It is recommended to use a cable of 0.3 to 0.75 mm² for the connection to the control circuit
terminals.
●
The wiring length should be 30 m (200 m for the terminal FM) at the maximum.
●
Use two or more parallel micro-signal contacts or twin contacts to prevent contact faults when
using contact inputs since the control circuit input signals are micro-currents.
●
To suppress EMI, use shielded or twisted cables for the control circuit terminals and run them away
from the main and power circuits (including the 200 V relay sequence circuit). For the cables
connected to the control circuit terminals, connect their shields to the common terminal of the
connected control circuit terminal. When connecting an external power supply to the terminal
PC, however, connect the shield of the power supply cable to the negative side of the external
power supply. Do not directly earth (ground) the shield to the enclosure, etc.
●
Always apply a voltage to the fault output terminals (A1, B1, C1, A2, B2, C2) via a relay coil, lamp, etc.
●
For the FR-A820-03160(55K) or higher and FR-A840-02160(75K) or higher, separate the wiring of
the control circuit away from the wiring of the main circuit.
Make cuts in rubber bush of the inverter side and lead the wires through.
Fig. 2-33:
Contacts
I001021E
I002375E
Fig. 2-34:
Wiring of the control circuit of the FR-A820-03160(55K) or higher and FR-A840-02160(75K)
or higher
Micro signal contacts
Twin contacts
Rubber bush
(viewed from inside)
Make cuts along the lines on the inside with
a cutter knife.
Wiring example
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......