(E) Environment setting parameters
Parameters
5 - 192
5.7.2 Reset
selection/disconnected
PU detection/PU stop selection
The reset input acceptance, disconnected PU (operation panel/parameter unit) connector detection
function and PU stop function can be selected.
The parameters above will not return to their initial values even if parameter (all) clear is executed.
The setting range for the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
The setting range for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
Setting Pr. 75 = any of "100 to 103 and 114 to 117" will enable the reset limit function. The setting
is available for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
Pr.
Name
Initial value
Setting range
Description
75
Reset selection/disconnected
PU detection/PU stop selection
14
0 to 3, 14 to 17
For the initial setting, reset is always
enabled, without disconnected PU
detection, and with the PU stop
function.
0 to 3, 14 to 17,
100 to 103, 114 to 117
E100
Reset selection
0
0
Reset input is always enabled.
1
Reset input is enabled only when the
protective function is activated.
E101
Disconnected PU detection
0
0
Operation continues even when the PU
is disconnected.
1
The inverter output is shut off when the
PU is disconnected.
E102
PU stop selection
1
0
Decelerates to a stop when the STOP
key is pressed in PU operation mode
only.
1
Decelerates to a stop when the STOP
key for PU is pressed in any of the PU,
external and communication operation
modes.
E107
Reset limit
0
0
Reset limit disabled
1
Reset limit enabled
Reset selection
Disconnected PU detection
PU stop selection
0, 100
Reset input always enabled
Operation continues even when PU
is disconnected.
Decelerates to a stop
when
is input in PU
operation mode only.
1, 101
Reset input enabled only when
protective function activated
2, 102
Reset input always enabled
Inverter output shut off when PU
disconnected.
3, 103
Reset input enabled only when
protective function activated
14 (Initial
value), 114
Reset input always enabled
Operation continues even when PU
is disconnected.
Decelerates to a stop
when
is input in any
of the PU, external and
communication operation
modes.
15, 115
Reset input enabled only when
protective function activated
16, 116
Reset input always enabled
Inverter output shut off when PU
disconnected.
17, 117
Reset input enabled only when
protective function activated
Tab. 5-70:
Setting of parameter 75
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......