Parameters
(D) Operation command and frequency command
FR-A800
5 - 271
When the X66 signal is ON, the NET operation mode is selected.
When the X16 signal is OFF, the PU operation mode is selected. Also, when "0" is set for Pr. 550 "NET
mode operation command source selection" and the communication option is not connected
(communication option is the command source), the PU operation mode is selected.
●
To switch between the Network operation mode and the External operation mode
Set Pr. 79 = "0" (initial value) or "2, "6" or "7". (When Pr. 79 = "7" and the X12 (MRS) signal is ON,
the operation mode can be switched.)
Set Pr. 340 "Communication startup mode selection" = "0" (initial value), "1" or "2".
Set "66" in one of Pr. 178 to Pr. 189 to assign the NET-External operation switching signal (X66)
to a terminal.
#
When the X66 signal is ON, Network operation mode is selected. When the X66 signal is OFF,
the External operation mode is selected.
When Pr. 550 "NET mode operation command source selection" = "0" (communication option
control source)" and no communication option is connected, the External operation mode is
selected.
When the X16 signal is OFF, the PU operation mode is selected. Also, when the X65 signal is
assigned, the operation mode follows the ON/OFF state of the X65 signal.
Pr. 340
setting
Pr. 79
setting
X65 signal state
Remarks
ON (PU)
OFF (NET)
10, 12
0 (initial value)
PU operation mode
NET operation
mode
⎯
1
PU operation mode
PU operation mode fixed
2
NET operation mode
NET operation mode fixed
3, 4
External/PU combined operation mode
External/PU combined operation mode fixed
6
PU operation mode
NET operation
mode
Switching between operation modes is
enabled while running.
7
X12 (MRS)
ON
Switching between the External
operation mode and PU operation mode
is enabled.
Output is shutoff in the External operation
mode.
X12 (MRS)
OFF
External operation mode
The operation mode is forcibly switched to
the External operation mode.
Tab. 5-105:
Operation mode switching by signal X65
Pr. 340
setting
Pr. 79
setting
X66 signal state
Remarks
ON (NET)
OFF (External)
0
(initial
value),
1, 2
0 (initial value)
External operation
⎯
1
PU operation mode
PU operation mode fixed
2
External operation
mode
Switching to PU operation mode is
disabled.
3, 4
External/PU combined operation mode
External/PU combined operation mode
fixed
6
External operation
Switching between operation modes is
enabled while running.
7
X12 (MRS)
ON
External operation
Output is shutoff in the External
operation mode.
X12 (MRS)
OFF
External operation mode
The operation mode is forcibly switched
to the External operation mode.
Tab. 5-106:
Operation mode switching by signal X66
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......