(E) Environment setting parameters
Parameters
5 - 224
Life display of the control circuit capacitor (Pr. 257)
●
The deterioration degree of the control circuit capacitor is displayed in Pr. 257.
●
In the operating status, the control circuit capacitor life is calculated from the energization time
and temperature, and is counted down from 100%. As soon as the control circuit capacitor life
falls below 10%, Pr. 255 bit 0 is turned ON and also a warning is output to the Y90 signal.
Life display of the main circuit capacitor (Pr. 258, Pr. 259)
(Standard models and IP55 compatible models)
●
The deterioration degree of the main circuit capacitor is displayed in Pr. 258.
●
With the main circuit capacitor capacity at factory shipment as 100%, the capacitor life is displayed
in Pr. 258 every time measurement is made. When the measured value falls to 85% or lower, Pr. 255
bit 1 is turned ON and also a warning is output to the Y90 signal.
●
Measure the capacitor capacity according to the following procedure and check the deterioration
degree of the capacitor capacity.
Check that the motor is connected and at a stop.
Set "1" (measuring start) in Pr. 259.
Switch the power OFF. The inverter applies DC voltage to the motor to measure the capacitor
capacity while the inverter is OFF.
#
After confirming that the power lamp is OFF, turn ON the power again.
,
Check that "3" (measurement complete) is set in Pr. 259, read Pr. 258, and check the deteriora-
tion degree of the main circuit capacitor.
NOTE
For accurate life measurement of the main circuit capacitor, wait three hours or longer after turn-
ing OFF. The temperature left in the main circuit capacitor affects measurement.
Pr. 259
Description
Remarks
0
No measurement
Initial value
1
Measurement start
Measurement starts when the power supply is
switched OFF
2
During measurement
Only displayed and cannot be set
3
Measurement complete
8
Forced end
9
Measurement error
Tab. 5-91:
Parameter 259
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......