Parameters
(G) Control parameters
FR-A800
5 - 675
5.16.10 Regenerative
brake
selection and DC feeding mode
●
When performing frequent start and stop operation, usage rate of the regenerative brake can be
increased by using the optional high-duty brake resistor (FR-ABR) or the brake unit (FR-BU2, BU,
FR-BU).
●
When using continuously in regenerative condition, use the power regeneration common con-
verter (FR-CV) or power regeneration converter (MT-RC). The high power factor converter
(FR-HC2) can be used also to reduce harmonics, improve power factor, and operate continuously
in the regenerative status.
●
It is possible to choose between the DC feeding mode 1, which will operate with DC power supply
(terminals P and N), and DC feeding mode 2, which will normally operate in AC power supply
(terminals R, S, and T) and operate in DC power supply (terminal P and N), such as batteries, at the
time of power failure.
●
While the power is supplied only to the control circuit, the reset operation when the power is
supplied to the main circuit can be selected.
The initial value or setting range for the standard model
The initial value or setting range for the separated converter type
The initial value or setting range for the IP55 compatible model
#
Available only with the standard model
Pr.
Name
Initial
value
Setting
range
Description
30
E300
Regenerative function
selection
0
10
0 to 2, 10,
11, 20, 21,
100 to 102,
110, 111,
120, 121
First digit: Regeneration unit selection ("0" for built-in brake,
"1" for high-duty brake resistor, "2" for FR-HC2 or FR-CV)
Second digit: Selection of the power supply terminal to the
inverter ("0" for AC, "1" for DC, "2" for AC and DC)
Third digit: Reset when the power is supplied to the main
circuit ("0" for reset, "1" for no reset)
For details, refer to the table below.
2, 10, 11,
102, 110,
111
0, 2, 10, 20,
100, 102,
110, 120
70
G107
#
Special regenerative
brake duty
0%
0 to 100%
Set the %ED of the built-in brake transistor operation.
599
T721
X10 terminal input
selection
0
1
0
Normally open input
1
Normally closed input (NC contact input specification)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......