Causes and corrective actions
Protective functions
6 - 24
Operation panel
indication
E.OLT
FR-LU-08
Stall prevention STP
Name
Stall prevention stop
Description
If the output frequency has fallen to 0.5 Hz by stall prevention operation and remains for 3 s, a
fault (E.OLT) appears and the inverter trips. OL appears while stall prevention is being activated.
When speed control is performed, a fault (E.OLT) appears and the inverter trips if frequency
drops to the Pr. 865 "Low speed detection" (initial value is 1.5 Hz) setting by torque limit
operation and the output torque exceeds the Pr. 874 "OLT level setting" (initial value is 150%)
setting and remains 3 s.
Check point
앫
Check the motor for the use under overload.
앫
Check that the Pr. 865 and Pr. 874 values are correct.
(Check the Pr. 22 "Stall prevention operation level" setting under V/F control and Advanced
magnetic flux vector control.)
앫
Check if a motor is connected under PM sensorless vector control.
Corrective action
앫
Reduce the load.
앫
Change the Pr. 22, Pr. 865, and Pr. 874 values. (Check the Pr. 22 setting under V/F control and
Advanced magnetic flux vector control.)
앫
For a test run without connecting a motor, select the PM sensorless vector control test
operation. (Refer to page 5-60.)
앫
Also check that the stall prevention (overcurrent) warning (OL) or the stall prevention
(overvoltage) warning (oL) countermeasure is taken.
Operation panel
indication
E.SOT
FR-LU-08
Motor step out
Name
Loss of synchronism detection
Description
The inverter trips when the motor operation is not synchronized. (This function is only available
under PM sensorless vector control.)
Check point
앫
Check that the PM motor is not driven overloaded.
앫
Check if a start command is given to the inverter while the PM motor is coasting.
앫
Check if a motor is connected under PM sensorless vector control.
앫
Check if a PM motor other than the MM-CF series is driven.
Corrective action
앫
Set the acceleration time longer.
앫
Reduce the load.
앫
If the inverter restarts during coasting, set Pr. 57 "Restart coasting time"
≠
"9999", and select
the automatic restart after instantaneous power failure.
앫
Check the connection of the IPM motor.
앫
For a test run without connecting a motor, select the PM sensorless vector control test
operation. (Refer to page 5-60.)
앫
Drive an IPM motor (MM-CF series)
앫
When driving an IPM motor other than MM-CF series, offline auto tuning must be
performed. (Refer to page 5-454.)
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Sensorless
Sensorless
Sensorless Vector
Vector
Vector
PM
PM
PM
PM
PM
PM
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......