Installation and wiring
Connection of stand-alone option units
FR-A800
2 - 89
2.10.6
Connection of the power regeneration common converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the inverter terminals
(P/+, N/-) and the power regeneration common converter (FR-CV) terminals as shown below so that
their symbols match with each other.
The FR-CV is applicable to FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
After making sure that the wiring is correct, set "2" in Pr. 30 "Regenerative function selection". (Refer
to page 5-675.)
Remove jumpers between terminals R/L1 and R1/L11 as well as between S/L2 and S1/L21, and
connect the power supply for the control circuit to terminals R1/L11 and S1/L21. Do not connect
anything to power input terminals (R/L1, S/L2, T/L3). Incorrect connection will damage the inverter.
(E.OPT (option fault) will occur. (Refer to page 6-26.)
Do not insert an MCCB between terminals P/+ and N/- (between terminals P/L+ and P/+ or
between N/L- and N/-). Connecting the opposite polarity of terminals N/- and P/+ will damage the
inverter.
Use Pr. 178 to Pr. 189 (input terminal function selection) to assign the terminals used for the X10
signal. (Refer to page 5-422.)
#
Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter
without connecting them will damage the power regeneration common converter.
,
Always connect terminal RDYB of the FR-CV to the inverter terminal where the X10 signal or the
MRS signal is assigned to. Always connect terminal SE of the FR-CV to the inverter terminal SD. Not
connecting these terminals may damage the FR-CV.
I001039E
Fig. 2-65:
Connection of the power regeneration common converter (FR-CV)
NOTES
The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1,
S2/L2, and T2/L3 must be matched.
Use the sink logic (factory setting) when the FR-CV is connected. It cannot be connected when the
source logic is selected.
Do not connect a DC reactor (FR-HEL) to the inverter when FR-CV is connected.
M
3~
#
Three-
phase AC
power
supply
,
Inverter
Dedicated stand-alone
reactor (FR-CVL)
FR-CV type
Power regeneration common
converter
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......