Control circuit
Installation and wiring
2 - 56
Safety stop function operation
ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and
SD to use the inverter. (In the initial status, terminals S1 and PC, S2 and PC, and SIC and SD are
respectively shorted with shorting wires.)
If any of the protective functions shown in the following table is activated, the terminal SO turns
OFF.
#
If the internal safety circuit is operated normally, the terminal SO remains ON until E.SAF is
displayed, and the terminal SO turns OFF when E.SAF is displayed.
,
SA is displayed when the terminals S1 and S2 are identified as OFF due to the internal safety circuit
failure.
$
If another fault occurs at the same time as E.SAF, the other fault can be displayed.
%
If another warning occurs at the same time as SA, the other warning can be displayed.
For more details, refer to the Safety stop function instruction manual (BCN-A23228-001).
(Find a PDF copy of this manual in the CD-ROM enclosed with the product.
Input
power
Internal
safety
circuit
status
Input terminal
,
Output
terminal
Inverter operation
enable signal
Operation panel
indication
S1
S2
SO
E.SAF
,
SA
$
OFF
—
—
—
OFF
Output shutoff
(Safe state)
Not
displayed
Not
displayed
ON
Normal
ON
ON
ON
Drive enabled
Not
displayed
Not
displayed
Normal
ON
OFF
OFF
#
Output shutoff
(Safe state)
Displayed
Displayed
Normal
OFF
ON
OFF
#
Output shutoff
(Safe state)
Displayed
Displayed
Normal
OFF
OFF
ON
Output shutoff
(Safe state)
Not
displayed
Displayed
Fault
ON
ON
OFF
Output shutoff
(Safe state)
Displayed
Not
displayed
,
Fault
ON
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Fault
OFF
ON
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Fault
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Tab. 2-22:
Description of Safety stop function operation
Fault record
Operation panel
indication
Fault record
Operation panel
indication
Option fault
E.OPT
Speed deviation excess detection E.OSD
Communication option fault
E.OP1
Signal loss detection
E.ECT
Parameter storage device fault
E.PE
Excessive position fault
E.OD
Retry count excess
E.RET
Brake sequence fault
E.MB1 to E.MB7
Parameter storage device fault
E.PE2
Encoder phase fault
E.EP
Operation panel power supply
short circuit/
RS-485 terminal power supply
short circuit
E.CTE
CPU fault
E.CPU
24 V DC power fault
E.P24
E.5 to E.7
Safety circuit fault
E.SAF
Internal circuit fault
E.13
Overspeed occurrence
E.OS
Tab. 2-23:
Indication of internal safety circuit failures
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......