(E) Environment setting parameters
Parameters
5 - 230
Operation example
●
The pulse output of Current average monitor signal (Y93) is indicated below.
●
For the terminal used for Y93 signal output, assign the function by setting "93 (positive logic)" or
"193 (negative logic)" in any of Pr. 190 to Pr. 194 (output terminal function selection). (This cannot
be assigned by setting in Pr. 195 "ABC1 terminal function selection" or Pr. 196 "ABC2 terminal
function selection".)
Pr. 556 "Data output mask time setting"
●
Immediately after acceleration/deceleration is shifted to constant-speed operation, the output
current is unstable (transitional state). Set the time for not obtaining (masking) transitional state
data in Pr. 556.
Pr. 555 "Current average time setting"
●
The output current average is calculated during start pulse (1 s) HIGH output. Set the time for
calculating the average current during start pulse output in Pr. 555.
Pr. 557 "Current average value monitor signal output reference current setting"
●
Set the reference (100%) for outputting the output current average value signal. The signal output
time is calculated with the following formula.
The output time range is 0.5 to 9 s. When the output current average value is less than 10% of the set-
ting value in Pr. 557, the output time is 0.5 s, and when it is more than 180%, the output time is 9 s.
For example, when Pr. 557 = "10 A" and the output current average value is 15 A:
15 A/10 A × 5 s = 7.5 s, thus the current average value monitor signal is Low output in 7.5 s intervals.
I001265E
Fig. 5-81:
Output of the pulse signal Y93
Output current average value
× 5 s (Output current average value 100%/5 s)
Pr. 557 setting value
Fig. 5-82:
Signal output time for the current average value
I001266E
From acceleration to constant speed operation
Output
frequency
Y93 signal
Data output mask time
When the speed has changed to constant from
acceleration/deceleration, Y93 signal is not output
for Pr. 556 time.
Start pulse
Output as Hi pulse shape for 1s (fixed). The output currents
are averaged during the time period set in Pr. 555.
Output current average value pulse
The averaged current value is output as low pulse shape for 0.5 to
9 s (10 to 180 %) during start pulse output.
Signal output time =
Output current average value (A)
× 5 s
Pr. 557 (A)
Maintenance timer pulse
The maintenance timer value (Pr. 503) is output as Hi
output pulse shape for 2 to 9 s (16000 h to 72000 h).
Signal output time =
Pr. 503 × 1000 h
× 5 s
40000 h
End pulse
output as low pulse shape
for 1 to 16.5 s
1 cycle (20 s)
Next cycle
Time
Output current average value
S
ig
n
al output tim
e [s]
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......