(G) Control parameters
Parameters
5 - 660
5.16.5
Adjustable 5 points V/F
By setting a desired V/F characteristic from the start up to the base frequency or base voltage with the
V/F control (frequency voltage/frequency), a dedicated V/F pattern can be generated.
Optimal V/F pattern matching the torque characteristics of the facility can be set.
●
By setting the V/F1 (first frequency voltage/first frequency) to V/F5 parameters in advance, a
desired V/F characteristic can be obtained.
●
For an example, with the equipment with large static friction factor and small dynamic friction
factor, large torque is required only at the start up, so a V/F pattern that will raise the voltage only
at the low-speed range is set.
Pr.
Name
Initial
value
Setting range
Description
71
C100
Applied motor
0
2
Standard motor (such as SF-JR)
Adjustable 5 points V/F
Others
Refer to page 5-434.
100
G040
V/F1(first frequency)
9999
0 to 590 Hz,
9999
Set each point of the V/F pattern
(frequency, voltage).
9999: Do not set V/F
101
G041
V/F1(first frequency voltage)
0 V
0 to 1000 V
102
G042
V/F2(second frequency)
9999
0 to 590 Hz,
9999
103
G043
V/F2(second frequency voltage)
0 V
0 to 1000 V
104
G044
V/F3(third frequency)
9999
0 to 590 Hz,
9999
105
G045
V/F3(third frequency voltage)
0 V
0 to 1000 V
106
G046
V/F4(fourth frequency)
9999
0 to 590 Hz,
9999
107
G047
V/F4(fourth frequency voltage)
0 V
0 to 1000 V
108
G048
V/F5(fifth frequency)
9999
0 to 590 Hz,
9999
109
G049
V/F5(fifth frequency voltage)
0 V
0 to 1000 V
I002752E
Fig. 5-327:
V/F characteristic
V/F
V/F
V/F
0
V/F5
V/F4
V/F3
V/F2
V/F1
Voltage
Frequency
Base
frequency
Pr. 3
Torque
boost
Pr. 0
Base
frequency
voltage
Pr. 19
V/F Characteristic
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......