Parameters
(N) Operation via communication and its settings
FR-A800
5 - 623
Setting items and set data
After completion of parameter settings, set the instruction codes and data, then start communication
from the computer to allow various types of operation control and monitoring.
Refer to page 5-505 for data formats (A, A1, A2, B, C, C1, D, E, E1, E2, E3, F).
Item
Read/
Write
Instruc-
tion
code
Data description
Number of
data digits
(Format)
Operation mode
Read
H7B
H0000: Network
operation
H0001: External
operation
H0002: PU operation, External/PU combined operation,
PUJOG operation
4 digits
(B.E/D)
Write
HFB
H0000: Network
operation
H0001: External
operation
H0002: PU operation (RS-485 communication operation via
PU connector)
4 digits
(A,C/D)
Mo
n
it
o
r
Output
frequency/
speed
Read
H6F
H0000 to HFFFF: Output frequency in 0.01Hz increments
(The display can be changed to the rotations per minute using
Pr. 37, Pr. 144 and Pr. 811. (Refer to page 5-324))
4 digits
(B.E/D)
Output
current
Read
H70
H0000 to HFFFF: Output current (hexadecimal)
Increment 0.01 A (FR-A820-03160(55K) or lower,
FR-A840-01800(55K) or lower)
Increment 0.1 A (FR-A820-03800(75K) or higher,
FR-A840-02160(75K) or higher)
4 digits
(B.E/D)
Output
voltage
Read
H71
H0000 to HFFFF: Output voltage (hexadecimal) in 0.1 V
increments
4 digits
(B.E/D)
Special
monitor
Read
H72
H0000 to HFFFF: Monitor data selected in the instruction code
HF3
4 digits
(B.E/D)
Special
monitor
selection
No.
Read
H73
Monitor selection data
(Refer to page 5-327 for details on selection No.)
2 digits
(B.E1/D)
Write
HF3
2 digits
(A1,C/D)
Fault record
Read
H74 to H77
H0000 to HFFFF: Two latest fault records
(Refer to page 6-5 for details on fault record read data.)
4 digits
(B.E/D)
Operation
command
(extended)
Write
HF9
Control input commands such as forward rotation signal (STF)
and reverse rotation signal (STR) can be set.
(For the details, refer to page 5-627.)
4 digits
(A, C/D)
Operation
command
Write
HFA
2 digits
(A1, C/D)
Tab. 5-274:
Setting of the instruction codes and data (1)
b15
b8 b7
b0
H74
H75
H76
H77
Second fault in past
Latest fault
Fourth fault in past
Third fault in past
Sixth fault in past
Fifth fault in past
Eighth fault in past
Seventh fault in past
0
b15
(HA0)
(H30)
0 1 1 0 0 0 0
b8
1
b7
0 1 0 0 0 0 0
b0
Fault record display example (instruction code H74)
With the read data H30A0
(Last fault : THT)
(Present fault : OPT)
Last fault
Present fault
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......