Parameters
(E) Environment setting parameters
FR-A800
5 - 203
5.7.11
Using the power supply exceeding 480V
To input a voltage between 480 V and 500 V to the 400 V class inverter, change the voltage protection
level.
●
To use a voltage between 480 V and 500 V, set Pr. 977 "Input voltage mode selection" = "1". The
setting is applied after a reset.
●
Setting Pr. 977 = "1" will change the voltage protection level to the one for the 500 V class.
●
The increased magnetic excitation deceleration level is changed to 740 V. (Use Pr. 660 "Increased
magnetic excitation deceleration operation selection" to select the increased magnetic excitation
deceleration.)
5.7.12 Parameter
write
selection
Whether to enable the writing to various parameters or not can be selected. Use this function to pre-
vent parameter values from being rewritten by misoperation.
Pr. 77 can be set at any time regardless of the operation mode or operation status. (Setting through
communication is unavailable.)
Pr.
Name
Initial value
Setting range Description
977
E302
Input voltage mode selection
0
0
400 V class voltage protection level
1
500 V class voltage protection level
NOTES
Stand-alone options (except line noise filter) cannot be used when inputting a voltage between
480 and 500 V.
The voltage protection level of the 200 V class inverters is not affected by the Pr. 977 setting.
Parameters referred to
Pr. 660
Increased magnetic excitation deceleration operation
selection
=>
Pr.
Name
Initial value
Setting range
Description
77
E400
Parameter write selection
0
0
Writing is enabled only during stop.
1
Parameter writing is disabled.
2
Parameter writing is enabled in any
operation mode regardless of the
operation status.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......