Parameters
(H) Protective function parameter
FR-A800
5 - 295
Electronic thermal O/L relay when using IPM motor (Pr. 9, E.THM)
●
This function detects the overload (overheat) of the motor and trips the inverter by stopping the
operation of the transistor at the inverter output side. (The operation characteristic is shown
below.)
●
Set the rated current (A) of the motor in Pr. 9. Performing IPM parameter initialization automati-
cally sets the rated current of the IPM motor. (Refer to page 5-73.)
●
Set "0" in Pr. 9 to avoid activating the electronic thermal O/L relay function; for example, when
using an external thermal relay for the motor.
(Note that the output transistor protection of the inverter is activated. (E.THT))
*
The % value denotes the percentage to the rated motor current.
– Protective function activated area: the area right of the characteristic curve
– Normal operation area: the area left of the characteristic curve
I002580E
Fig. 5-122:
Electronic thermal relay function operation characteristic (MM-CF)
NOTES
The internal accumulated heat value of the electronic thermal relay function is reset to the initial
value by the inverter's power reset and reset signal input. Avoid unnecessary reset and power-
OFF.
When using a PM motor other than MM-CF, set the free thermal parameters (Pr. 600 to Pr. 604) in
accordance with the motor characteristic.
The transistor protection thermal O/L relay is activated early when the Pr. 72 "PWM frequency
selection" is increased.
80 100 120 140 160 200 220 240 260 280 300
50
60
70
0
60
120
180
240
2000 r/min
(133.33 Hz) or lower
3000 r/min
(200 Hz)
2000 r/min
(133.33 Hz) or lower
3000 r/min
(200 Hz)
Range for the
transistor
protection
Current [%]
T
h
ermal
r
e
la
y oper
a
tion time [s]
(s) u
n
it displ
a
y
in this region
(min) unit displa
y
in
this r
e
gion
Th
e
rm
a
l rel
a
y
operation time
[min]
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......