Parameters
Parameter List
FR-A800
5 - 21
PID pr
e
-char
ge func
tion
760
A616
Pre-charge fault selection
0, 1
1
0
761
A617
Pre-charge ending level
0 to 100%, 9999
0.1%
9999
762
A618
Pre-charge ending time
0 to 3600 s, 9999
0.1 s
9999
763
A619
Pre-charge upper detection level
0 to 100%, 9999
0.1%
9999
764
A620
Pre-charge time limit
0 to 3600 s, 9999
0.1 s
9999
765
A656
Second pre-charge fault selection
0, 1
1
0
766
A657
Second pre-charge ending level
0 to 100%, 9999
0.1%
9999
767
A658
Second pre-charge ending time
0 to 3600 s, 9999
0.1 s
9999
768
A659
Second pre-charge upper detection
level
0 to 100%, 9999
0.1%
9999
769
A660
Second pre-charge time limit
0 to 3600 s, 9999
0.1 s
9999
Mo
n
it
o
r
func
ti
on
774
M101
Operation panel monitor selection 1
1 to 3, 5 to 14, 17 to 20, 22
to 36, 38, 40 to 46, 50 to
57, 61, 62, 64, 67, 71 to
74, 87 to 98, 100, 9999
1
9999
775
M102
Operation panel monitor selection 2
1
9999
776
M103
Operation panel monitor selection 3
1
9999
⎯
777
A681
4 mA input check operation frequency
0 to 590 Hz, 9999
0.01 Hz
9999
T053
⎯
778
A682
4 mA input check filter
0 to 10 s
0.01 s
0 s
T054
⎯
779
N014
Operation frequency during
communication error
0 to 590 Hz, 9999
0.01 Hz
9999
⎯
788
G250
Low speed range torque characteristic
selection
0, 9999
1
9999
⎯
791
F070
Acceleration time in low-speed range
0 to 3600 s, 9999
0.1 s
9999
⎯
792
F071
Deceleration time in low-speed range
0 to 3600 s, 9999
0.1 s
9999
⎯
799
M520
Pulse increment setting for output
power
0.1, 1, 10, 100, 1000 kWh
0.1 kWh
1 kWh
⎯
800
G200
Control method selection
0 to 6, 9 to 14, 20, 100 to
106, 109 to 114
1
20
⎯
802
G102
Pre-excitation selection
0, 1
1
0
To
rq
u
e
com
m
an
d
803
G210
Constant output range torque
characteristic selection
0, 1, 10, 11
1
0
5-84,
804
D400
Torque command source selection
0, 1, 3 to 6
1
0
5-84,
805
D401
Torque command value (RAM)
600 to 1400%
1%
1000%
5-84,
806
D402
Torque command value
(RAM, EEPROM)
600 to 1400%
1%
1000%
5-84,
Spee
d l
imit
807
H410
Speed limit selection
0 to 2
1
0
808
H411
Forward rotation speed limit/speed
limit
0 to 400 Hz
0.01 Hz
60 Hz
50 Hz
809
H412
Reverse rotation speed limit/reverse-
side speed limit
0 to 400 Hz, 9999
0.01 Hz
9999
Fu
n
c
ti
o
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to page
Cu
st
o
m
e
r
setting
FM
CA
Tab. 5-2:
Parameter overview (by number) (20)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...