(A) Application parameters
Parameters
5 - 526
Basic configuration of PID control
Pr. 128 = "10, 11" (deviation value signal input)
●
Pr. 128 = "20, 21" (measured value input)
1145
A643
Second PID deviation
limit
9999
0 to 100%, 9999
Refer to Pr. 553.
(Y205 signal is
output.)
Set the second PID control.
For how to enable the second
PID control, refer to page 5-551.
1146
A644
Second PID signal
operation selection
0
0 to 3, 10 to 13
Refer to Pr. 554.
1147
A661
Second output
interruption detection
time
1 s
0 to 3600 s, 9999 Refer to Pr. 575.
1148
A662
Second output
interruption detection
level
0 Hz
0 to 600 Hz
Refer to Pr. 576.
1149
A663
Second output
interruption cancel level
1000%
900 to 1100%
Refer to Pr. 577.
I001230E
Fig. 5-255:
System configuration when Pr. 128 = 10, 11 (using an external (PID) controller)
I001231E
Fig. 5-256:
System configuration when Pr. 128 = 20 or 21 (set/feedback value at the inverter)
Pr.
Name
Initial
value
Setting range
Description
[
[
Kp 1+
+Td S
1
Ti S
•
•
* Set "0" to Pr. 868 "Terminal 1 function assignment". When Pr. 868
≠
"0", PID control is invalid.
Set point
Deviation signal
Kp: Proportionality constant; Ti: Integral time; S: Operator; Td: Differential time
Motor
Manipulated
variable
Terminal 1 *
0 to
±
10 V DC
(0 to
±
5 V)
Feedback signal (measured value)
PID operation
Inverter circuit
To outside
[
[
Kp 1+
+Td S
1
Ti S
•
•
Note that the input of terminal 1 is added to the set point of terminal 2 as a set point.
Set "0" to Pr. 858 "Terminal 4 function assignment". When Pr. 858
≠
"0", PID control is invalid.
Set point
Kp: Proportionality constant; Ti: Integral time; S: Operator; Td: Differential time
Motor
Manipulated
variable
Terminal 4
Feedback signal (measured value)
PID operation
Inverter circuit
4 to 20 mA DC
(0 to 5 V, 0 to 10 V)
0 to 5 V DC
(0 to 10 V, 4 to 20 mA)
Pr. 133 or
terminal 2
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......