Parameters
Speed control under Real sensorless vector control, vector control, PM sensorless vector control
FR-A800
5 - 81
5.3.2
Setting procedure of vector control (speed control)
Fig. 5-11:
Setting procedure of vector control (speed control)
NOTES
The speed command setting range under vector control is 0 to 400 Hz.
The carrier frequency is limited during vector control. (Refer to page 5-222.)
For vector control for a motor with a resolver, refer to the Instruction Manual of the FR-A8APR.
Vector
Vector
Vector
Perform secure wiring.
(Refer to page 2-67.)
Set the applied motor and encoder.
(Pr. 71, Pr. 359 (Pr. 852), Pr. 369 (Pr. 851)) (Refer to page 2-74.)
Set the operation command. (Refer to page 5-263.)
Set the torque limit. (Pr. 810)
(Refer to page 5-84.)
Select the control method. (Pr. 800) (Refer to page 5-56.)
As required
앫
Perform offline auto tuning. (Pr. 96) (Refer to page 5-67.)
앫
Select online auto tuning. (Pr. 95) (Refer to page 5-465.)
앫
Easy gain tuning (Refer to page 5-100.)
앫
Adjusting the speed control gain manually (Refer to page 5-102.)
Select Pr. 800 = "0" (speed control), "2" (speed/torque
switchover) or "4" (speed/position switchover) to enable
speed control.
Select the start command and speed command.
Set the overheat protection of the motor. (Pr. 9)
(Refer to page 5-292.)
Set the motor capacity (kW) in Pr. 80 "Motor capacity", and set
the number of motor poles in Pr. 81 "Number of motor poles".
(V/F control is performed when the setting is "9999" (initial
value).)
Install a vector control compatible option.
Set Pr. 71 "Applied motor", Pr. 359(Pr. 852) "Encoder rotation
direction" and Pr. 369(Pr. 851) "Number of encoder pulses"
according to the applied motor and encoder.
Set the rated motor voltage and the rated motor frequency.
(Pr. 83, Pr. 84) (Refer to page 2-74.)
Set the rated motor voltage (V) in Pr. 83 "Rated motor voltage",
and set the rated motor frequency (Hz) in Pr. 84 "Rated motor
frequency".
Test run
Set the rated motor current (A) in Pr. 9 "Electronic thermal O/L
relay".
When using the SF-V5RU or a motor equipped with a thermal
sensor, set Pr. 9 = "0A".
Set the motor capacity and number of motor poles.
(Pr. 80, Pr. 81) (Refer to page 5-56.)
Set the option to be used. (Pr. 862)
Set Pr. 862 "Encoder option selection" according to the option to
be used (refer to page 5-64).
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......