Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Parameters
5 - 102
Adjusting the speed control gain manually (Pr. 819 = "0" No easy gain tuning)
●
The speed control gain can be adjusted for the conditions such as abnormal machine vibration,
acoustic noise, slow response, and overshoot.
●
Pr. 820 "Speed control P gain 1" = "60 % (initial value)" is equivalent to 120 rad/s (speed response
of a single motor). (Equivalent to the half the rad/s value during Real sensorless vector control or
with the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher during vector control.)
Setting this parameter higher speeds up the response, but setting this too high causes vibration
and acoustic noise.
●
Setting Pr. 821 "Speed control integral time 1" lower shortens the return time to the original speed
during speed fluctuation, but setting it too low causes overshoot.
The value in parentheses is applicable during Real sensorless vector control or with the FR-A820-
03800(75K) or higher and FR-A840-02160(75K) or higher during vector control.
Performing PM parameter initialization changes the settings. (Refer to page 5-71.)
●
Actual speed gain is calculated as below when load inertia is applied.
JM: Motor inertia
JL: Load inertia converted as the motor axis inertia
Fig. 5-25:
Setting of the proportional gain
I001483E
I001484E
Fig. 5-26:
Speed characteristic at load fluctuation
Actual speed gain = Speed gain of a single motor ×
JM
JM + JL
Proportional gain
200 (100) rad/s
120 (60) rad/s
60 %
(Initial value
)
100 %
Pr. 820
Setting
Load
fluctuation
Speed
Decreasing the integral time shortens the return time taken.
Since increasing the proportional gain enhances the
response level and decreases the speed fluctuation.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......