Parameters
Control method
FR-A800
5 - 71
Initializing the parameters required for the PM sensorless vector control (Pr. 998)
●
PM parameter initialization sets parameters required for driving an IPM motor MM-CF.
●
The offline auto tuning enables the operation with an IPM motor other than MM-CF and with SPM
motors.
●
Two MM-CF IPM parameter initialization methods are available; setting Pr. 998 "PM parameter
initialization", and selecting
(IPM parameter initialization) mode on the operation panel.
●
To use a motor capacity that is one rank lower than the inverter capacity, set Pr. 80 "Motor capacity"
before performing IPM parameter initialization.
●
When Pr. 998 = "3003, 8009, or 9009", the monitor is displayed and the frequency is set using the
motor rotations per minute. To use frequency to display or set, set Pr. 998 = "3103, 8109, or 9109".
●
Set Pr. 998 = "0" to change the PM sensorless vector control parameter settings to the parameter
settings required to drive an induction motor.
●
When using an IPM motor other than MM-CF, set Pr. 998 = "8009, 8109, 9009, or 9109". The setting
can be made after performing offline auto tuning.
Pr.
Name
Initial
value
Setting
range
Description
998
E430
PM parameter
initialization
0
0
Parameter settings for an induction motor
(frequency)
The parameter settings
required to drive an
induction motor are set.
3003
For IPM motor MM-CF.
Parameter setting (rotations per minute)
The parameters settings
required to drive an IPM
motor are set.
3103
For IPM motor MM-CF.
Parameter setting (frequency)
8009
The parameters settings required to drive
an IPM motor other than MM-CF are set.
(rotations per minute) (after tuning)
The parameters settings
required to drive an IPM
motor are set.
(Set Pr. 71 "Applied motor"
and perform offline auto
tuning in advance. (Refer to
page 5-454.))
8109
The parameters settings required to drive
an IPM motor other than MM-CF are set.
(frequency) (after tuning)
9009
The parameters settings required to drive
an SPM motor are set. (rotations per
minute) (after tuning)
The parameters settings
required to drive an SPM
motor are set.
(Set Pr. 71 "Applied motor"
and perform offline auto
tuning in advance. (Refer to
page 5-454.))
9109
The parameters settings required to drive
an SPM motor are set.
(frequency) (after tuning)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......