Installation and wiring
Peripheral devices
FR-A800
2 - 5
400 V class
Assumes the use of a Mitsubishi 4-pole standard motor with the power supply voltage of 400 V AC
50 Hz.
NOTES
The above shows a selection example for the ND rating. For selecting the SLD rating, LD rating, or
HD rating, refer to the Technical News (MF-X-121) contained in the enclosed CD-ROM.
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic
contactor according to the inverter model, and select cables and reactors according to the motor
output.
When the breaker on the inverter's input side trips, check for the wiring fault (short circuit), dam-
age to internal parts of the inverter etc. The cause of the trip must be identified and removed
before turning ON the power of the breaker.
Motor
output
[kW]
Applicable inverter
model
Molded case circuit breaker (MCCB)
or
earth leakage circuit breaker (ELB)
(NF, NV type)
Input-side magnetic contactor
Power factor improving (AC or DC)
reactor
Power factor improving (AC or DC)
reactor
Without
With
Without
With
0.4
FR-A840-00023(0.4K)
5A
5A
S-T10
S-T10
0.75
FR-A840-00038(0.75K)
5A
5A
S-T10
S-T10
1.5
FR-A840-00052(1.5K)
10A
10A
S-T10
S-T10
2.2
FR-A840-00083(2.2K)
10A
10A
S-T10
S-T10
3.7
FR-A840-00126(3.7K)
20A
15A
S-T10
S-T10
5.5
FR-A840-00170(5.5K)
30A
20A
S-T21
S-T12
7.5
FR-A840-00250(7.5K)
30A
30A
S-T21
S-NT21
11
FR-A840-00310(11K)
50A
40A
S-T21
S-T21
15
FR-A840-00380(15K)
60A
50A
S-N25
S-T21
18.5
FR-A840-00470(18.5K)
75A
60A
S-N25
S-N25
22
FR-A840-00620(22K)
100A
75A
S-N35
S-N25
30
FR-A840-00770(30K)
125A
100A
S-N50
S-N50
37
FR-A840-00930(37K)
150A
125A
S-N65
S-N50
45
FR-A840-01160(45K)
175A
150A
S-N80
S-N65
55
FR-A840-01800(55K)
200A
175A
S-N80
S-N80
75
FR-A840-02160(75K)
⎯
225A
⎯
S-N95
90
FR-A840-02600(90K)
⎯
225A
⎯
S-N150
110
FR-A840-03250(110K)
⎯
225A
⎯
S-N180
132
FR-A840-03610(132K)
⎯
400A
⎯
S-N220
160
FR-A840-04320(160K)
⎯
400A
⎯
S-N300
185
FR-A840-04810(185K)
⎯
400A
⎯
S-N300
220
FR-A840-05470(220K)
⎯
500A
⎯
S-N400
250
FR-A840-06100(250K)
⎯
600A
⎯
S-N600
280
FR-A840-06830(280K)
⎯
600A
⎯
S-N600
Tab. 2-3:
Breakers and contactors (400 V class)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......