Parameters
(A) Application parameters
FR-A800
5 - 551
●
Example of protective function measured value limit (Pr. 760 = "1")
Setting multiple PID pre-charge functions
●
When the second pre-charge function is set, two sets of pre-charge functions can be switched for
use. The second pre-charge function is enabled by turning ON the RT signal.
●
The second pre-charge function parameters and signals function in the same way as the following
parameters and signals of the first pre-charge function. Refer to the first pre-charge function when
setting the second pre-charge functions.
I002705E
Fig. 5-273:
Reaching of pre-charge limit by the measured amount
Classification
First pre-charge function parameters
Second pre-charge function parameters
Pr.
Name
Pr.
Name
Parameter
760
Pre-charge fault selection
765
Second pre-charge fault selection
761
Pre-charge ending level
766
Second pre-charge ending level
762
Pre-charge ending time
767
Second pre-charge ending time
763
Pre-charge upper detection level
768
Second pre-charge upper detection
level
764
Pre-charge time limit
769
Second pre-charge time limit
Tab. 5-234:
Parameters for setting multiple PID pre-charge functions
Classification
First pre-charge function parameters
Second pre-charge function parameters
Signal
Name
Signal
Name
Input signal
X77
Pre-charge end command
X78
Second pre-charge end command
Output signal
Y49
During pre-charge operation
Y50
During second pre-charge operation
Y51
Pre-charge time over
Y52
Second pre-charge time over
Y53
Pre-charge level over
Y54
Second pre-charge level over
Tab. 5-235:
I/O signals for multiple PID pre-charge functions
NOTES
The second PID pre-charge function is valid also when the first pre-charge function is set to invalid
and the second pre-charge function is set.
When "10" (second function enabled only during constant-speed operation) is set to Pr. 155, the
second PID function is not selected even if the RT signal turns ON.
STF
Y49
Y53
ALM
E.PCH
Measured value [PSI]
When Pr. 760 = "1",
output is shut off after the motor decelerates to a stop.
Time
Time
Pr. 127
Pr. 763
Output frequency [Hz]
0 Hz
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......