Parameter settings for a motor with encoder
Installation and wiring
2 - 74
Parameter settings for the motor under vector control
Values in
i
ndicate initial values.
Offline auto tuning is required (Refer to page 5-67.)
Set this parameter according to the motor.
Use the thermal protector input provided with the motor.
●
When using the inverter with the SF-V5RU (1500 r/min series), refer to the table below to set Pr. 83
"Rated motor voltage" and Pr. 84 "Rated motor frequency".
Motor name
Pr. 9
"
Electronic
thermal O/L
relay
"
Pr. 71
"
Applied
motor
"
Pr. 80
"
Motor
capacity
"
Pr. 81
"
Number of
motor poles
"
Pr. 359/
Pr. 852
"
Encoder
rotation
direction
"
Pr. 369/
Pr. 851
"
Number of
encoder
pulses
"
Mitsubishi
standard
motor
SF-JR
Rated motor
current
0
Motor
capacity
Number of
motor poles
1
1024
SF-JR 4P
1.5 kW or
lower
Rated motor
current
20
Motor
capacity
4
1
1024
SF-HR
Rated motor
current
40
Motor
capacity
Number of
motor poles
1
1024
Others
Rated motor
current
0(3)
Motor
capacity
Number of
motor poles
Mitsubishi
constant-
torque motor
SF-JRCA 4P
Rated motor
current
1
Motor
capacity
4
1
1024
SF-HRCA
Rated motor
current
50
Motor
capacity
Number of
motor poles
1
1024
Others
Rated motor
current
1(13)
Motor
capacity
Number of
motor poles
Vector control
dedicated
motor
SF-V5RU
(1500 r/min
series)
0
30
Motor
capacity
4
1
2048
SF-V5RU
(except for
1500 r/min
series)
0
1(13)
Motor
capacity
4
1
2048
SF-THY
0
30(33)
Motor
capacity
4
1
2048
Other manu-
facturer's
standard
motor
⎯
Rated motor
current
0(3)
Motor
capacity
Number of
motor poles
Other manu-
facturer's con-
stant-torque
motor
⎯
Rated motor
current
1(13)
Motor
capacity
Number of
motor poles
PM motor
Refer to the instruction manual of the FR-A8APR.
Tab. 2-38:
Motor for vector control and parameter setting
Motor
capacity
SF-V5RU
Motor
capacity
SF-V5RU
200 V
400 V
200 V
400 V
Pr. 83 [V] Pr. 84 [Hz] Pr. 83 [V] Pr. 84 [Hz]
Pr. 83 [V] Pr. 84 [Hz] Pr. 83 [V] Pr. 84 [Hz]
1.5 kW
188
52
345
52
18.5 kW
171
51
346
51
2.2 kW
188
52
360
52
22 kW
160
51
336
51
3.7 kW
190
52
363
52
30 kW
178
51
328
51
5.5 kW
165
51
322
51
37 kW
166
51
332
51
7.5 kW
164
51
331
51
45 kW
171
51
342
51
11 kW
171
51
320
51
55 kW
159
51
317
51
15 kW
164
51
330
51
Tab. 2-39:
Rated motor voltage and rated motor frequency (when using SF-V5RU
)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......