Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Parameters
5 - 100
Execution procedure for easy gain tuning (Pr. 819 = "2" Load inertia ratio manual input)
Easy gain tuning (load inertia ratio manual input) is valid in the speed control mode under Real sen-
sorless vector control, the speed control and position control modes under vector control, and the
speed control mode under PM sensorless vector control.
Set the load inertia ratio for the motor in Pr. 880 "Load inertia ratio".
Set "2" (easy gain tuning enabled) in Pr. 819 "Easy gain tuning selection". When set, Pr. 820 "Speed
control P gain 1" and Pr. 821 "Speed control integral time 1" are set automatically.
Operation is performed with the adjusted gain from the next operation.
Perform a test run, and set the response level in Pr. 818 "Easy gain tuning response level setting".
Setting this parameter higher improves the trackability for commands, but setting it too high
causes vibration. (The response level can be adjusted during operation when Pr. 77 "Parameter
write selection" = "2" (parameters can be written during operation).)
NOTES
When Pr. 819 = "1, 2" is set, even if the Pr. 819 setting value is returned to "0" after tuning is per-
formed, the data that was set in each parameter is retained in the tuning results.
If good precision cannot be obtained even after executing easy gain tuning, because of external
disturbances or other reasons, perform fine adjustment manually. At this time, set the setting
value of Pr. 819 to "0" (no easy gain tuning).
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......