Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 383
●
When Pr. 54 "FM/CA terminal function selection" = "87, 88, 89, or 90" (remote output), the CA type
inverter can output any analog current from the terminal CA.
●
Terminal CA output [mA] = 20 [mA] × (analog remote output value – 1000)/100
Where the output range is 0 to 20 mA.
●
When Pr. 158 "AM terminal function selection" = "87, 88, 89, or 90", an analog voltage can be output
from the terminal AM.
●
Terminal AM output [V] = 10 [V] × (analog remote output value – 1000)/100
The output range is –10 V to +10 V regardless of the Pr. 290 "Monitor negative output selection"
setting.
I002634E
Fig. 5-181:
Terminal CA output
I002635E
Fig. 5-182:
Terminal AM output
20
1100
1200
800
1000
0
Output current [mA]
Analog remote output value [%]
Terminal CA
10
1100
1200
-10
900
800
1000
0
Terminal AM
Analog remote output value [%]
Output voltage [V]
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......