Parameters
(T) Multi-Function Input Terminal Parameters
FR-A800
5 - 409
5.12.6
Bias and gain for torque (magnetic flux) and set voltage (current)
The magnitude (slope) of the torque can be set as desired in relation to the torque setting signal (0 to
5 V DC, 0 to 10 V DC, or 4 to 20 mA).
Use Pr. 73 "Analog input selection" or Pr. 267 "Terminal 4 input selection" to switch among input 0 to
5 V DC, 0 to 10 V, and 4 to 20 mA. (Refer to page 5-389.)
The parameter number in parentheses is the one for use with the LCD operation panel and the
parameter unit.
Changing the function of analog input terminal
The initial value for terminal 1 used as analog input is set to speed setting auxiliary (speed limit aux-
iliary), and terminal 4 is set to speed command (speed control). To use the analog input terminal as
torque command, torque limit, or magnetic flux command, set Pr. 868 "Terminal 1 function assign-
ment", Pr. 858 "Terminal 4 function assignment" to change the function. (Refer to page 5-394.)
The magnetic flux command is valid under vector control only.
Pr.
Name
Initial
value
Setting
range
Description
C16 (919)
T110
Terminal 1 bias command (torque)
0%
0 to 400%
Set the torque (magnetic flux) of the bias side of
terminal 1 input.
C17 (919)
T111
Terminal 1 bias (torque)
0%
0 to 300%
Set the converted % on bias side voltage of
terminal 1 input.
C18 (920)
T112
Terminal 1 gain command (torque)
150%
0 to 400%
Set the torque (magnetic flux) of the gain
(maximum) of terminal 1 input.
C19 (920)
T113
Terminal 1 gain (torque)
100%
0 to 300%
Set the converted % on the gain side voltage of
terminal 1 input.
C38 (932)
T410
Terminal 4 bias command (torque)
0%
0 to 400%
Set the torque (magnetic flux) of the bias side of
terminal 4 input.
C39 (932)
T411
Terminal 4 bias (torque)
20%
0 to 300%
Set the converted % on the bias side current
(voltage) of terminal 4 input.
C40 (933)
T412
Terminal 4 gain command (torque)
150%
0 to 400%
Set the torque (magnetic flux) of the gain
(maximum) of terminal 4 input.
C41 (933)
T413
Terminal 4 gain (torque)
100%
0 to 300%
Set the converted % on gain side current
(voltage) of terminal 4 input.
241
M043
Analog input display unit switchover
0
0
% display
Select the unit for analog input
display.
1
V/mA
display
Sensorless
Sensorless
Sensorless Vector
Vector
Vector
PM
PM
PM
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......