(M) Monitor display and monitor output signal
Parameters
5 - 368
●
According to the inverter condition, the ON/OFF operation of each signal is as shown below.
OFF during power failure or undervoltage.
Output is shutoff in conditions like a fault and when the MRS signal is ON.
OFF while power is not supplied to the main circuit power supply.
●
Operation under Real sensorless vector control, vector control and PM sensorless vector control
–
When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON.
(stays ON during operation.)
–
When the inverter output frequency reaches Pr. 13 "Starting frequency" or higher, the output
of Inverter running (RUN) turns ON. The signal is OFF while the inverter is stopped, the DC
injection brake is operating, during tuning at start-up, or during pre-excitation.
–
The Inverter running 2 (RUN2) signal is ON while the inverter is running or the start signal is
ON. (When the inverter's protective function is activated or the MRS is ON, the RUN2 signal
turns OFF.)
–
The Inverter running and start command is ON (RUN3) signal output is ON while the inverter
is running or the start signal is ON.
Output
signal
Start
signal OFF
(during
stop)
Start
signal ON
(during
stop)
Start
signal ON
(running)
DC
injection
brake
operation
Automatic restart after
instantaneous power failure
Coasting
Restart-
ing
Start
signal ON
Start
signal OFF
Start
signal ON
Start
signal OFF
ON
ON
ON
ON
OFF
ON
RY2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
RUN
OFF
OFF
ON
OFF
OFF
OFF
ON
RUN2
OFF
OFF
ON
OFF
OFF
OFF
ON
RUN3
OFF
ON
ON
ON
ON
OFF
ON
OFF
ON
Tab. 5-141:
Output signal output
I002622E
Fig. 5-166:
Ready and motor running signals
STF
RH
RY
RY2
MRS
RUN
RUN2
RUN3
Pre-excitation
(0 speed control)
Power
supply
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
Time
OFF
OFF
OFF
OFF
OFF
Reset
processing
Pr. 13
Ou
tput fr
equenc
y
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......