Frequently-used parameters (simple mode parameters)
Basic operation
4 - 12
Initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower.
Initial value for the FR-A820-00105(1.5K) to FR-A820-00250(3.7K) and the FR-A840-00052(1.5K) to
FR-A840-00126(3.7K).
Initial value for the FR-A820-00340(5.5K), FR-A820-00490(7.5K), FR-A840-00170(5.5K), and
FR-A840-00250(7.5K).
#
Initial value for the FR-A820-00630(11K) to FR-A820-03160(55K), FR-A840-00310(11K) to
FR-A840-01800(55K).
,
Initial value for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
$
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
%
For the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
&
The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower is set
to the 85% of the rated inverter current.
+
Initial value for the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
'
Initial value for the FR-A820-00630(11K) or higher and FR-A840-00310(11K) or higher.
(
FM denotes the initial value for the FM type inverter that has the terminal FM, and CA denotes the
initial value for the CA type inverter that has the terminal CA.
9
H000
C103
Electronic
thermal O/L relay
0.01 A
Rated
inverter
current
Protects the motor from heat.
Set the rated motor current.
0–3600 A
79
D000
Operation mode
selection
1
0
0–4, 6, 7
Select the start and frequency command
sources.
125
T022
Terminal 2
frequency setting
gain frequency
0.01 Hz 60 Hz 50 Hz
0–590 Hz
Allows the frequency at the maximum
potentiometer setting (5 V in the initial
setting) to be changed.
126
T042
Terminal 4
frequency setting
gain frequency
0.01 Hz 60 Hz 50 Hz
0–590 Hz
Allows the frequency at the maximum
current input (20 mA in the initial setting)
to be changed.
160
E440
User group read
selection
1
0
0, 1, 9999
Restricts the parameters that are read by
the operation panel and parameter unit.
998
E430
PM parameter
initialization
1
0
0, 3003,
3103,
8009,
8109,
9009, 9109
Selects the PM sensorless vector control
and set the parameters that are required to
drive an PM motor.
999
E431
Automatic
parameter setting
1
9999
1, 2, 10, 11,
12, 13, 20,
21, 30, 31,
9999
Changes parameter settings as a batch.
The target parameters include
communication parameters for the
Mitsubishi's human machine interface
(GOT) connection and the parameters for
the rated frequency settings of 50 Hz/
60 Hz.
Pr.
Pr.
group
Name
Unit
Initial value
(
Range
Application
Refer
to
page
FM
CA
Tab. 4-9:
Simple mode parameters (2)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......