(C) Motor constant parameters
Parameters
5 - 458
Setting
●
To perform tuning, set the following parameters about the motor.
Set Pr. 71 "Applied motor" according to the motor to be used. According to the Pr. 71 setting, the
range of the motor constant parameter setting values and units can be changed. (For other setting
values of Pr. 71, refer to page 5-434.)
●
For the tuning accuracy improvement, set the following parameter when the motor constant is
known in advance.
The setting is valid only when both of the Pr. 707 (Pr. 744) and Pr. 724 (Pr. 745) settings are other
than "9999".
First
motor Pr.
Second
motor Pr.
Name
Setting for a PM motor other than
MM-CF
Setting for MM-CF
80
453
Motor capacity
Motor capacity (kW)
Set by the IPM
parameter initialization
(Refer to page 5-71.)
81
454
Number of motor poles
The number of motor poles (2 to 12)
9
51
Electronic thermal O/L
relay
Rated motor current (A)
84
457
Rated motor frequency
Rated motor frequency (Hz)
83
456
Rated motor voltage
Rated motor voltage (V)
Rated motor voltage (V)
written on the rated
plate
71
450
Applied motor
8090, 8093 (IPM motor)
330 and 333
96
463
Auto tuning setting/status 1
11
Tab. 5-186:
Set the parameters before performing tuning
Motor
Pr. 71 setting
Motor constant parameter
Ω
, mH and A unit setting
Motor constant parameter
Internal data setting
IPM motor
MM-CF
330
333 (334)
Other than MM-CF
8090
8093 (8094)
SPM motor
9090
9093 (9094)
Tab. 5-187:
Motor selection
NOTES
If PM sensorless vector control is performed, tuning cannot be performed even when Pr. 96 =
"101" is set. If MM-CF is set to the applied motor, tuning cannot be performed even when Pr. 96 =
"1, 101" is set.
First
motor Pr.
Second
motor Pr.
Name
Setting for a PM motor other than
MM-CF
Setting for MM-CF
702
743
Maximum motor
frequency
The maximum motor frequency [Hz]
9999 (initial value)
707
744
Motor inertia (integer)
Motor inertia
Jm = Pr. 707 × 10^(– Pr. 724) [kg/m
2
]
9999 (initial value)
724
745
Motor inertia (exponent)
725
746
Motor protection current
level
Maximum current level of the motor [%]
9999 (initial value)
Tab. 5-188:
Parameter settings to improve the tuning accuracy
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......