Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 381
Remote output data retention (REM signal, Pr. 495)
●
If the power supply is reset (including a power failure) while Pr. 495 = "0 (initial value) or 10", t the
REM signal output is cleared. (The terminal ON/OFF status is determined by the settings in Pr. 190
to Pr. 196.) "0" is also set in Pr. 496 and Pr. 497.
●
When Pr. 495 = "1 or 11", the remote output data is saved in EEPROM before the power supply is
turned OFF. This means that the signal output after power restoration is the same as before the
power supply was turned OFF. However, when Pr. 495 = "1", the data is not saved during an inverter
reset (terminal reset, reset request via communication).
●
When Pr. 495 = "10 or 11", the signal before the reset is saved even during an inverter reset.
I002631E
Fig. 5-179:
ON/OFF example for positive logic
NOTES
The output terminals that have not been assigned with a REM signal by Pr. 190 to Pr. 196 do not
turn ON/OFF even if "0 or 1" is set in the terminal bits of Pr. 496 and Pr. 497. (ON/OFF is performed
with the assigned functions.)
When Pr. 495 = "1 or 11" (remote output data retention at power OFF), take measures such as con-
necting R1/L11 with P/+, and S1/L21 with N/- so that the control power is retained. If the control
power is not retained, the output signal after turning ON the power is not guaranteed to work.
When connecting the high power factor converter FR-HC2 or the converter unit FR-CC2, assign the
instantaneous power failure detection (X11) signal to an input terminal to input the IPF signal
from the FR-HC2/FR-CC2 to the terminal for X11 signal.
Parameters referred to
Pr. 190 to Pr. 196
(output terminal function selection)
=>
∗
Pr. 495 = 1, 11
Inverter
reset time
(about 1 s)
REM signal held
REM signal is saved
REM signal clear
REM
REM
OFF
OFF OFF
Power
supply
Power
supply
Pr. 495 = 0, 10
ON/OFF example for positive logic
Signal condition during a reset
Pr. 495 = 0, 1
Pr. 495 = 10, 11
Reset
Reset
REM
REM
OFF
ON
ON
* When Pr. 495 = "1", the signal condition saved in EEPROM
(condition of the last power OFF) is applied.
ON
ON
ON
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......