Parameters
(G) Control parameters
FR-A800
5 - 687
To detect the regenerative status during deceleration faster (Pr. 884)
Since a rapid change in bus voltage cannot be handled by bus voltage level detection during the re-
generation avoidance operation, deceleration is stopped by detecting the change in bus voltage and
if it is equal or lower than Pr. 883 "Regeneration avoidance operation level".
Set the detectable bus voltage change rate as the detection sensitivity in Pr. 884 "Regeneration avoid-
ance at deceleration detection sensitivity". A larger set value increases the detection sensitivity.
Limit regeneration avoidance operation frequency (Pr. 885)
●
It is possible to assign a limit to the output frequency corrected (rise) by the regeneration
avoidance operation.
●
Limit of the frequency is output frequency (frequency before regeneration avoidance operation)
+ Pr. 885 "Regeneration avoidance compensation frequency limit value" for during acceleration
and constant speed.
During deceleration, when the frequency increases due to the regeneration avoidance operation
and exceeds the limit value, the limit value will be retained until the output frequency is reduced
to be the half the Pr. 885 setting.
●
When the frequency that have increased by the regeneration avoidance operation exceeds Pr. 1
"Maximum frequency", it will be limited to the maximum frequency.
●
By setting to Pr. 885 = "9999", regeneration avoidance operation frequency limitation is disabled.
●
Set using the motor rated slip frequency as a guideline. Raise the setting value if the overvoltage
protection function (E.OV[]) operation at the start of deceleration.
NOTE
When the setting value is too small (detection sensitivity is not good), detection will not be possi-
ble, and regeneration avoidance will operate even with the bus voltage change caused by a
change in the input power.
Rated motor slip frequency
=
Synchronized speed at the time of base
frequency - rated rotation speed
× Rated motor frequency
Synchronized speed at the time of base
frequency
Fig. 5-345:
Limit the output frequency
I001260E
Output
fr
e
q
uenc
y [
H
z]
Pr. 885
Time
Pr. 885/2
Output frequency [Hz]
Limit level
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......