Causes and corrective actions
Protective functions
6 - 28
Operation panel
indication
E.PUE
FR-LU-08
PU disconnection
Name
PU disconnection
Description
앫
The inverter trips if communication between the inverter and PU is suspended, e.g. the
operation panel or parameter unit is disconnected, when the disconnected PU
disconnection function is valid in Pr. 75 "Reset selection/disconnected PU detection/PU stop
selection".
앫
The inverter trips if communication errors occurred consecutively for more than permissible
number of retries when Pr. 121 "Number of PU communication retries" ≠ "9999" during the
RS-485 communication.
앫
The inverter trips if communication is broken within the period of time set in Pr. 122 "PU
communication check time interval" during the RS-485 communication via the PU
connector.
Check point
앫
Check that the operation panel or the parameter unit is connected properly.
앫
Check the Pr. 75 setting.
Corrective action
Fit the operation panel or the parameter unitsecurely.
Operation panel
indication
E.RET
FR-LU-08
Retry count excess
Name
Retry count excess
Description
The inverter trips if the operation cannot be resumed properly within the number of retries set in
Pr. 67 "Number of retries at fault occurrence".
Check point
Find the cause of the fault occurrence.
Corrective action
Eliminate the cause of the error preceding this error indication.
Operation panel
indication
E.PE2
FR-LU-08
PR storage alarm
Name
Parameter storage device fault (main circuit board)
Description
The inverter trips if a fault occurs in the parameter stored. (EEPROM failure)
Check point
⎯
Corrective action
Please contact your sales representative.
Operation panel
indication
CPU
FR-LU-08
CPU Fault
E. 5
Fault 5
E. 6
Fault 6
E. 7
Fault 7
Name
CPU fault
Description
The inverter trips if the communication fault of the built-in CPU occurs.
Check point
Check for devices producing excess electrical noises around the inverter.
Corrective action
앫
Take measures against noises if there are devices producing excess electrical noises around
the inverter.
앫
Please contact your sales representative.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......