Parameters
(H) Protective function parameter
FR-A800
5 - 297
Motor permissible load level setting (Pr. 607, Pr. 608)
The electronic thermal O/L relay operation characteristic can be changed by setting the permissible
load level according to the motor characteristics.
Electronic thermal O/L relay pre-alarm (TH) and warning signal (THP signal)
●
If the accumulated electronic thermal value reaches 85% of the Pr. 9 or Pr. 51 setting, electronic
thermal O/L relay function pre-alarm (TH) is displayed and the electronic thermal O/L relay pre-
alarm (THP) signal is output. If the value reaches 100% of the Pr. 9 setting, the motor thermal
protection (E.THM/E.THT) is activated to shut off the inverter output. The inverter output is not
shut off with the TH display.
●
The inverter output is not shut off with the warning signal (THP).
●
For the terminal used for THP signal output, set "8 (positive logic)" or "108 (negative logic)" in any
of Pr. 190 to Pr. 196 (output terminal function selection) to assign the function.
I002851E
Fig. 5-124:
Example of motor permissible load setting (when Pr. 9 = "100% of the inverter rating")
I001138E
Fig. 5-125:
Prealarm signal output
NOTE
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
0
60
120
180
240
80
100
120
140
160
180
200
Inverter output power (%)
(% to the inverter rated current)
Range for the
transistor
protection
T
h
ermal r
e
la
y op
er
ation
time [s]
Motor permissible load 200%
Motor permissible load 150% (Initial value)
Motor permissible load
110%
Time
100 %: Electronic thermal O/L relay activation value
Electronic thermal
O/L relay alarm
(THP)
Electronic thermal
relay function
operation level
OFF
ON
ON
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......